3. Selection of Location

This unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial
environment. If installed as a household appliance it could cause electromagnetic
interference.
The VRV OUTDOOR units should be installed in a location that meets the following requirements:
1. The foundation is strong enough to support the weight of the unit and the floor is flat to prevent
2. The space around the unit is adequate for servicing and the minimum space for air inlet and air
3. There is no danger of fire due to leakage of inflammable gas.
4. Ensure that water cannot cause any damage to the location in case it drips out the unit (e.g. in
5. The piping length between the outdoor unit and the indoor unit may not exceed the allowable
6. Select the location of the unit in such a way that neither the discharged air nor the sound
7. Make sure that the air inlet and outlet of the unit are not positioned towards the main wind
CAUTION
1. An inverter air conditioner may cause electronic noise generated from AM broadcasting.
Installation Manual REYQ96MTJU
vibration and noise generation.
outlet is available.
(refer to figure 1 and choose one of both possibilities)
<
>
If installed as a single unit
(Pattern 1)
B1
1
≥3/8
≥ 3/8
A
(Pattern 2)
B2
≥ 2
1
≥ 2
A
(Pattern 3)
≥11 3/4
2
≥7 7/8
1
1. Front side
2. No limit to wall height
3. Suction side
case of a blocked drain pipe).
piping length. (see "Example of connection")
generated by the unit disturb anyone.
direction. Frontal wind will disturb the operation of the unit. If necessary, use a windscreen to
block the wind.
Examine where to install the main air conditioner and electric wires, keeping proper distances
away from stereo equipment, personal computers, etc.
1
2
3
5
If the electric wave of AM broadcasting is particularly weak, keep distances of 10ft. or more and
use conduit tubes for power and transmission lines.
<
When installed in serial
(Pattern 1)
≥ 3/8
≥3/4
1
≥ 3/8
≥3/4
(Pattern 2)
≥ 2
≥3 7/8
1
≥ 2
≥ 3 7/8
2
(Pattern 3)
≥11 3/4
≥ 7 7/8
≥15 3/4
≥15 3/4
1
2
1. indoor unit
2. Branch switch, overcurrent breaker
4
3. remote controller
4. cool/heat selector
5. personal computer or radio
(in.)

Selection of Location

>
H1≤59
A≥19 5/8
H1=59+X
A≥19 5/8+X/2
B1
H2≤19 5/8
B1≥11 3/4
B2≥3 7/8
A
H2=19 5/8 + Y
B1≥11 3/4+Y/2
B2≥3 7/8+Y/2
B2
B1
B2
A
A
1
3
(in.)
141