Download Print this page

Technical Data - Siemens OpenAir GDB111.1E/KN Quick Manual

Communicative damper actuators knx / pl-link

Advertisement

Technical data

Power supply
Operating voltage
Frequency
Power consumption
Function data
Positioning time for
nominal rotation angle
Nominal torque
Maximum torque
Nominal / maximum
rotation angle
Direction of rotation
Connection cables
Cable length
Power supply
Communication
Communication
Communication protocol
Degree of protection
Degree of protection
Safety class
Environmental conditions
Applicable standard
Operation
Transport
Storage
8 / 10
Siemens
Smart Infrastructure
G..B111.1E/..
at 50 Hz
Actuator holds
Actuator rotates
G..B111.1E/..
GDB..
GLB..
GDB..
GLB..
Adjustable by tool or over bus
Number of cores and cross-sectional area 2 x 0.75 mm
Number of cores and cross-sectional area 2 x 0.75 mm
Connection type
Bus load
Degree of protection acc. to EN 60529
(see mounting instruction)
Safety class acc. to EN 60730
Climatic conditions
Mounting location
Temperature general
Humidity (non condensing)
Climatic conditions
Temperature
Humidity
Climatic conditions
Temperature
Humidity
AC 24 V ± 20 % (SELV)
or
AC 24 V class 2 (US)
50/60 Hz
1 VA / 0.5 W
3 VA / 2.5 W
150 s (50 Hz)
125 s (60 Hz)
5 Nm
10 Nm
< 7 Nm
< 14 Nm
90° / 95° ± 2°
Clockwise (CW) /
Counter-clockwise (CCW)
0.9 m
2
2
KNX-TP (galvanically isolated)
5 mA
IP54
III
IEC 60721-3-x
Class 3K5
Indoors
0...50 °C
5...95 % r. F.
Class 2K3
-25...70 °C
5...95 % r. h.
Class 1K3
-5...45 °C
5...95 % r. h.
A6V11753386_en--_a
2020-02-25

Advertisement

loading

This manual is also suitable for:

Openair glb111.1e/kn