KNX Group Objects
No.
Name in ETS
Object
function
1
Fault information
Transmit
2
Fault state
Transmit
3
Fault transmission
Receive
4
Setpoint
Receive
5
Damper position
Transmit
9
Overridden
Transmit
10
Override position 1
Receive
11
Override position 2
Receive
12
Opening direction
Read-only
6 / 10
Siemens
Smart Infrastructure
Flags
Data point type KNX
C R W T
U ID
1 1
0
1
0
219.001
1 1
0
1
0
1.005
1 0
1
0
1
1.003
1 1
1
0
1
5.001
1 1
0
1
0
5.001
1 1
0
1
0
1.002
1 1
1
0
1
1.003
1 1
1
0
1
1.003
1 1
0
0
0
1.012
DPT_Name
Format
_AlarmInfo
6 Byte
_Alarm
1 bit
_Enable
1 bit
_Scaling
1 Byte
_ Scaling
1 Byte
_Bool
1 bit
_Enable
1 bit
_Enable
1 bit
_Invert
1 bit
Range
Unit
---
cf. Description below
---
0 = No alarm
1 = Alarm
---
0 = Disable
1 = Enable
0...100%
%
%
0...100%
---
0 = False
1 = True
---
0 = Disable
1 = Enable
---
0 = Disable
1 = Enable
---
0 = Not Inverted
1 = Inverted