Commissioning and parameterization
The following parameters are checked or set during engineering and commissioning in the
ETS engineering tool.
Parameter
Tab card "standard"
Adaptive positioning On / Off
Backup timeout
Backup mode
Backup position
Tab card "advanced"
Hysteresis (COV)
damper position
Min. repetition time
damper position
Minimum damper
position
Maximum damper
position
Override position 1
Override position 2
A6V11753386_en--_a
2020-02-25
Range
Description
Adaption of actual (if mechanically limited)
opening range to position feedback 0...100%
Off = No adaption / On = Adaption active
0..60 min
Time interval to detect communication
interruption.
0 min = disabled
If disabled, the actuator drives to the last received
setpoint until a new valid setpoint is received.
Backup position
Actuator behavior when the communication
Keep last position
timeout has been exceeded (no setpoint received
within the defined time interval).
▪ Backup position: Actuator drives to defined
position
▪ Keep last position: Actuator keeps position
without flow control
0...100%
Position the damper drives to in case of
communication interruption
1...20%
Threshold for the damper position. COV below
this value are not sent over the bus
10...900 s
Minimum waiting time until a COV above the
hysteresis threshold is sent over the bus
Electronic lower position limit
0...100%
0...100%
Electronic upper position limit
Damper position which can be triggered by the
0...100%
corresponding group object (with override priority)
0...100%
Damper position which can be triggered by the
corresponding group object (with override priority)
Factory settings
Off
30 min.
Backup position
50%
1%
10 s
0%
100%
0%
100%
5 / 10