6.2 WIRING AND ADDRESSING

ITEMS
Wiring for Modbus
RS485
Modbus Address
Network Connection
1592038710 Gas Leak Detector Modbus GB 01.12.2016
Modbus connector is CN4.
Pin 1 GND
Pin 2 + TX/RX non-inverting signals
Pin 3 - TX/RX inverting signals
The 3-pin connections are designed for a 2-conductor wire with
a common drain shield.
Hexadecimal Address Switches.
Used to set a unique address for the sensor when multiple
sensors are connected to a controller.
Valid addresses are 0-247.
Modbus addressing can be selected by the combined settings
on the hexadecimal dial switches SW1 and SW2.
Addresses 0-15 are selectable with switch SW1 (the least
significant portion of the address). SW2 scales the addresses
by a factor of 16 (the most significant portion of the address).
NOTE: Address 0 is reserved to enable the master to broadcast
to all of the detector slave devices.
Addresses 248-255 (0x8F – 0xFF) are reserved.
Addresses 254 (0xEF) and 255 (0xFF) are reserved for setting
the Modbus communications Baud rates.
GDS41M-GDS66M-GDI41M-GDI66M