SureTest
®
Circuit Analyzer and
SureTest
®
w/AFCI Instructions
Introduction
The SureTest
®
family of circuit analyzers were designed to
troubleshoot branch circuits quickly, easily and accurately.
They have a patented technology that allows them to test
branch circuits under a full load condition to identify
hidden problems behind the wall that will not be
found with traditional testing methods.
Product Features
• True RMS
• Measures voltage drop under 12, 15 and 20-amp load
• Line voltage
• Peak voltage
• Frequency
• Ground impedance
• Hot and neutral conductor impedances
• Ground-neutral voltage
• Identifies proper wiring in 3-wire receptacles
• Identifies false (bootleg) grounds
• Verifies dedicated circuits (with 61-176 adapter)
• Tests GFCIs for proper operation
• Tests AFCI's for proper operation (61-155)
• Includes carrying case
• Includes 1-ft. extension cord
General Operation
The SureTest
®
Circuit Analyzer, #61-154 and SureTest® Circuit Analzer,
#61-155 take only seconds to test each outlet and circuit under a full load.
They check for various wiring conditions, including: correct wiring, polarity
reversal, hot/ground reversal and no ground. A simple programming menu
gives access to measurements of line voltage, voltage drop under a full load
condition, ground-neutral voltage and line impedances. The ground fault
circuit interrupter (GFCI) test is performed separately and will disrupt the
electrical supply if a functional GFCI is present
Sold by:
http://www.TWAcomm.com
Toll Free: (877) 892-2666
#61-154
The SureTest
®
(AFCI) test to ensure that AFCI breakers protecting the circuit have been
#61-155
installed correctly and are operating properly. This test is performed sepa-
rately in accordance with UL1436, and will disrupt the electrical supply if a
functional AFCI is present.
For proper troubleshooting of a branch circuit, insert the SureTest into the fur-
thest receptacle from the panel. Any discrepancies from a normal reading dur-
ing a measurement indicate that a problem has been detected in the circuit.
Allow at least 20 seconds between insertions. Repeatedly inserting the SueTest
into a receptacle will cause the unit to heat up which may affect the accuracies.
WARNING: Do not use on outputs from UPS systems, light
dimmers or square wave generating equipment.
General Specifications
Case construction:
Operating Range:
Display:
Dimensions:
Weight:
Environmental Specifications
Operating Temp.:
Storage Temp.:
Humidity:
Altitude:
Safety:
Input Rating:
Overvoltage Category:
Pollution Degree 2:
w/AFCI, #61-155, will also test arc fault circuit interrupter
ABS UL 94 V/0/5VA rated
108 to 132 Volts
97x32 Pixel Graphics Display with backlight
6.5" x 3" x 1"
9.4oz
0° C to 50° C
0° C to 50° C
<80% RH
2000m (6667 ft.)
Designed to IEC 1010-1 UL3111
150VAC Category III
Cat III: Distribution level mains, fixed installations
Cat II: Local level mains, appliances, portable
equipment
Cat I: Signal level, special equipment or parts of
equipment, telecommunications, electronics
Do not operate in environments where conductive
pollutants may be present
2

Advertisement

loading

Summary of Contents for IDEAL SureTest 61-154

  • Page 1 #61-154 The SureTest ® w/AFCI, #61-155, will also test arc fault circuit interrupter (AFCI) test to ensure that AFCI breakers protecting the circuit have been #61-155 installed correctly and are operating properly. This test is performed sepa- rately in accordance with UL1436, and will disrupt the electrical supply if a functional AFCI is present.
  • Page 2 Accuracy Menu Buttons Line Voltage: 108.0 - 132.0VAC 1.0% +/- 1 digit The SureTest model ST-2D uses two buttons to navigate through the mea- surement menu. The down arrow button ( ↓ ) moves the unit forward to the Peak Voltage 151.0 - 185.0VAC 1.0% +/- 1 digit...
  • Page 3 SureTest checks for proper wiring. While it is performing this test, the IDEAL logo will be displayed on the LCD. The SureTest model ST-2D will analyze the neutral and ground conductors The SureTest 61-154 checks for the following conditions to identify a potential false ground condition.
  • Page 4: Troubleshooting Tips

    SureTest Measurements Troubleshooting Tips Use the down arrow ( ↓ ) and side arrow (→ ) buttons to navigate through The line voltage tests are conducted without a load. If these results are not the measurement menu as outlined in the menu buttons section of this man- met, it could be a problem with the circuit, or a load on the circuit.
  • Page 5 Voltage Drop Measurements Troubleshooting Tips There are three tests within the voltage drop menu. Measurement Expected Problem Possible Possible Measurement Icon Result Causes Solutions Voltage Drop <5% High - Too much load - Redistribute the Voltage Drop at 15-Amp load voltage on the branch load on the circuit...
  • Page 6 Line Impedance Measurements Troubleshooting Tips There are three tests within the line impedance menu. Measurement Expected Problem Possible Possible Measurement Icon Result Causes Solutions Hot conductor <0.48Ω/ High - Too much load - Redistribute the Hot conductor impedance Ω impedance foot of 14 conductor on branch circuit load on the circuit gauge wire impedance - Undersized...
  • Page 7 GFCI Testing AFCI Testing (#61-155 only) The SureTest ® applies 6mA though a fixed resistor to trip the GFCI. A func- The SureTest® w/AFCI applies a high current pulse onto the line within 8 tional GFCI will disconnect the power. The reset button for the GFCI may be consecutive half-cycles in accordance with UL1436.
  • Page 8: Optional Accessories

    Optional Accessories #61-183 Lighting Circuit Adapter This adapter allows the operator to use #61-175 Ground Continuity Adapter the SureTest on residential lighting cir- This adapter allows the operator to verify that a cabinet or equipment chas- cuits to verify that bedroom lighting cir- sis has been properly bonded to the system ground.
  • Page 9 Quick Reference Guide Measurement Menu Locating High Resistance Connections Troubleshooting to identify the cause of the high impedance within the elec- Line Voltage Menu trical system is actually quite simple. First measure the voltage drop at the furthest receptacle from the panel on the branch circuit under test. If the →...
  • Page 10: Lifetime Limited Warranty

    Any implied warranties arising out of the sale of an IDEAL product, includ- ing but not limited to implied warranties of merchantability and fitness for a particular purpose, are limited to the above.

This manual is also suitable for:

Suretest 61-155