Voltage Drop Measurements
There are three tests within the voltage drop menu.
Measurement
Voltage Drop at 15-Amp load
Voltage Drop at 12-Amp load
Voltage Drop at 20-Amp load
The National Electrical Code recommends 5% as the maximum voltage drop
for branch circuits for reasonable efficiency (NEC article 210-19. FPN 4).
High voltage drop could be an indication of a high resistance connection
within the circuit, undersized wire for the load or length of run, or a defective
device on the branch circuit.
All of the voltage drop measurements are taken under an actual 12-Amp load
and extrapolated for 15 amp and 20 amp measurements. This allows the
user to test a 15-Amp rated circuit at full capacity or 80% capacity, and test a
20-Amp rated circuit under a full capacity. Voltage drop under a 15 amp
load is the first measurement within this menu selection. Pressing the side
arrow button (→ ) moves the unit from measurement to measurement within
the line voltage menu. Pressing the down arrow button ( ↓ ) moves the unit
to the next menu selection – Ground-Neutral Voltage.
Sold by:
http://www.TWAcomm.com
Toll Free: (877) 892-2666
Icon
15A
%
DROP
12A
%
DROP
20A
%
DROP
9
Troubleshooting Tips
Measurement Expected Problem
Result
Voltage Drop
<5%
High
voltage
drop
Ground-Neutral Voltage Measurement
There is only one test within the Ground-Neutral Voltage menu. In a single-
phase circuit, high ground-neutral voltage indicates excessive leakage
between the neutral and ground conductors. In a 3-phase circuit with a
shared neutral, a high ground-neutral voltage could also indicate unbalanced
load between the three phases, or harmonic distortion on the shared neutral.
A reading of less than 2 Volts usually indicates a usable outlet. An excessive
ground-neutral voltage may result in inconsistent or intermittent equipment
performance. Pressing the down arrow button ( ↓ ) moves the unit to the
next menu selection – Line Impedance.
Troubleshooting Tips
Measurement Expected Problem Possible
Result
Causes
Ground-Neutral
<2V
High G-N - Current leaking
Voltage
voltage
from neutral
to ground
- Unbalanced
3-phase system
- Harmonic content - Oversize neutral or
returning on neutral de-rate transformer
in 3-phase system
10
Possible
Possible
Causes
Solutions
- Too much load
- Redistribute the
on the branch
load on the circuit
circuit
- Undersized wire
- Check code
for length of run
requirements and
re-wire if
necessary
- High resistance
- Locate high
connection within
resistance
the circuit or at the connection/device
panel
and repair/replace
Possible
Solutions
- Identify source of
leakage (multiple
l bonding points)
- Check load balance
and re-distribute load
to dissipate heat