INSTALLER SETTING
80

Water supply off temp. during cooling

Determine leaving water temperature when the unit is turned off. This function is used for
preventing condensation on the floor in cooling mode
• In the installer setting list, select Water supply off temp. during cooling category, and press
[OK] button to move to the detail screen.
Function
Value
Water supply off temperature
cooling water
temperature
FCU Use / not use
OK
Default
Setting Rang
16
25~16
use
Use / Not Use
- Stop temp. : cut-off temperature. Stop temp. is valid when FCU is installed.
- FCU : determines if FCU is installed or not.
- Example : If Stop temp. is set as '10' and FCU is 'Use' and actually FCU is NOT installed in the
water loop, the unit stop operation in cooling mode when the leaving water
temperature is below 10 °C.
- Example : If Stop temp. is set as '10' and FCU is 'Not use' and actually FCU is installed in the
water loop, the Stop temp. is not used and the unit do NOT stop operation in cooling
mode when the leaving water temperature is below 10 °C.
CAUTION
!
FCU Installation
• If FCU is used, related 2way valve should be installed and connected to the unit PCB.
• If FCU is set as 'Not use' but FCU or 2way valve is NOT installed, the unit can do abnormal
operation.