Chapter 4) 7SR158 - Data Communications
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Analog Input Deadband: 34
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit)
Point
Name
FW#
Index
(Description)
174 V Phase A Max
175 V Phase B Max
176 V Phase C Max
177 V Phase AB Max
178 V Phase BC Max
179 V Phase CA Max
192 Freq Last Trip
196 Frequency Max
5.4 Additional Settings
The following relay settings are provided for configuration of the DNP 3.0 implementation when available and are
common to all ports using this protocol.
Setting Name
Unsolicited
DISABLED, ENABLED
Mode
Destination
0 - 65534
Address
DNP3
Application
5, 6 ... 299, 300
Timeout
Chapter 4 - Page 54 of 66
or 2 (16-Bit Analog Input with Flag)
or 3 (32-Bit Analog Input w/o Flag)
or 4 (16-Bit Analog Input w/o Flag)
or 5 (Single Precision, floating point Analog Input with Flag)
or 2 (16-Bit Analog Input w/o Time)
or 3 (32-Bit Analog Input with Time)
or 4 (16-Bit Analog Input with Time)
or 5 (Single Precision, floating point Analog Input w/o Time)
or 7 (Single Precision, floating point Analog Input with Time)
or 2 (32-Bit)
or 3 (Single Precision, floating point)
Default
Change Event
Assigned Class
(1, 2, 3 or none)
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
Range/Options
Default
Default
Variation
Variation
Default
Static
Event
Multiplier
Object 30
Object 32
2
4
2
4
2
4
2
4
2
4
2
4
5
7
2
4
Default
Setting
DISABLED
As Required
0
As Required
10s
As Required
© 2013 Siemens Protection Devices Limited
Default
Deadband
0.010
100.000
0.010
100.000
0.010
100.000
0.010
100.000
0.010
100.000
0.010
100.000
1.000
1.000
100.000
1.000
Notes
Setting is only visible
when any port
Protocol is set to
DNP3.
Setting is only
visible when DNP3
Unsolicited Events
set to Enabled.
Setting is only visible
when any port
Protocol is set to
DNP3.

Advertisement

loading