SET OWNID 2003
SET PMP bl bh
Sets the power management parameters.
bl is the lower battery level (the threshold where the charging of
the battery is switched on) and bh is the higher battery level (the
charging is switched off).
Nothing.
Both bl and bh are expressed in volts
means 7.2 V). Default values (factory programmed) are 65 and 72,
meaning 6.5 and 7.2 volts respectively.
To change the switch-on threshold to 6.3 and the switch-off thresh-
old to 7.0 volts:
SET PMP 63 70
SET SLOT storage samples
Configures the input sampling and storing intervals.
storage represents the time (in seconds) elapsed between two
slots stored in the internal memory, while samples represents the
numbers of samples used to build the average that will be stored.
Nothing.
The default storage is 900 (15 minutes) and samples is 3 (3 sam-
ples per quarter of an hour).
To sample the inputs (sensors) every minute and build an hourly
average:
SET SLOT 3600 60
To sample the inputs once per hour and store the values as they
are:
SET SLOT 3600 1