SETUP
OUTPUTS
OPTIONS
MIN OFF
OR
MIN ON
Fig. 49. Setup - Outputs - Options - Min Off/On Time.
SETUP
SETUP
OUTPUTS
OUTPUTS
OPTIONS
OPTIONS
MIN OFF
MIN ON
0
SEC
ENTER
ENTER
MINIMUM
MINIMUM
OFF TIME
ON TIME
FOR RELAYS
FOR RELAYS
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
1.3.3.2. MIN OFF
This is the minimum number of seconds of "off time" or
"on time" for all relays.
1. Press the u button to display the Min Off/On value.
2. Use the p and q buttons to increase/decrease the
desired number of seconds from 0 to 990 seconds
0
SEC
in 10 second increments.
Default: 0 (zero)
Range: 0 to 990 seconds
3. Press the u button to accept the seconds and
display the DI OPTIONS.
M24610A
NOTES:
1.
2.
3.
23
MIN ON
or
The minimum off time applies to all relay
outputs.
When minimum off time is active, relays
waiting to be energized display a flashing
square underneath the relay number on the
home screen.
If the minimum off time is not equal to zero
(0), the minimum off time activates at power-
up. To manually override, press the t button at
any time.
62-0255—09