Download Print this page

Honeywell T775U 2000 Series Installation Instructions Manual page 38

Electronic stand-alone controller

Advertisement

T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
SUMMARY MENU
The Summary menu provides the ability to view the
schedule (E1 and E2 times) for each relay for each day of
the week.
NOTE: Scheduling must be enabled for the
Summary menu to display. Enabling the
schedule is determined in the Setup process
for the Output Options (see page 22).
MENU
SUMMARY
Fig. 86. Summary Example - Monday Settings.
For each relay, the Summary display indicates the time
and temperature (in parenthesis) for each of the two
scheduled events E1 and E2.
1. Press the MENU button to view the menu.
2. Use the p and q buttons to highlight SUMMARY.
3. Press the u button to display the Summary settings.
4. Use the u button to scroll forward through each day
of the week (Monday, Tuesday, Wednesday,
Thursday, Friday, Saturday, and Sunday).
5. While viewing a specific day, use the p and q
buttons to cycle through the individual relay
schedules for that day.
When finished, press the HOME button to return to the
home display screen.
If programmed for Reset control, the Summary setpoints
display as "RES" instead of a temperature value. For
example, the display would show:
MONDAY
STAGES
E1: 06:00AM (RES)
E2: 06:00PM (05)
TROUBLESHOOTING
Power Loss
The date and time settings are retained for 24 hours after
a power outage. After a power loss of more than 24 hours,
the date and time settings may need to be reentered. All
other settings are stored permanently.
Errors and Diagnostics
The controller provides an error message and diagnostic
status as described below.
62-0255—09
MENU
SUMMARY
MONDAY
RELAY 1-2
E1: 06:00AM (72)
E2: 06:00PM (65)
M24629
- indicating Reset
- setback/offset degrees
Error Message
There is a two-character error code that displays in
response to controller software problems:
EE
EEPROM Failure— The values read back from
the EEPROM are not the same as written into the
EEPROM. This error cannot be field repaired. Replace
the device.
Diagnostic Messages
There are two diagnostic messages that can display in
response to sensor problems. The diagnostic codes that
can flash on the display are:
– –
Sensor Open or Shorted — Two dashes display
when a sensor (typically temperature) is open or
shorted. An open circuit is considered anything
greater than 1570 ohms (greater than 300F), shorted
anything less than 770 ohms (less than -73F). Which-
ever stages are operating with this sensor cease to
control (meaning relays go to OFF and proportional
outputs go to zero percent).
This message can also mean that the sensor is pro-
grammed, but not physically connected.
-60°F or 270°F (-51°C or 132°C) Blinking
Temperature Out of Range — The temperature
display blinks when the sensed temperature range is
outside of the display range, below -60°F (-51°C) or
above 270°F (132°C). The displayed value remains at
that displayed limit and control continues. Controller
continues to function unless an open or shorted state
is detected.
Blinking relay status
Relay Minimum Off Time is Active — On the home
screen, each relay's indicator (¢) blinks while the
relay's minimum off time is active.
SPECIFICATIONS
Power: 24, 120, or 240 Vac; 50/60 Hz
A separate earth ground is required for any power
source.
Power Consumption:
• 8 VA maximum at 60 Hz
• 10 VA maximum at 50 Hz
Operating & Storage Temperature Ambient Rating:
• -40°F to 125°F (-40°C to 52°C) @ 50 Hz
• -40°F to 140°F (-40°C to 60°C) @ 60 Hz
Relative Humidity: 5% to 95% non-condensing
Relay Contact Output Ratings (N.O. and N.C.):
• 1/2 hp; 9.8 AFL, 58.8 ALR @ 120 Vac
• 1/2 hp; 4.9 AFL, 29.4 ALR @ 240 Vac
• 125 VA pilot duty @ 120/240 Vac
• 10A @ 24 Vac (resistive)
Modulating Outputs:
• 0-10 Vdc; drive a minimum of 2,000 Ohms
• 2-10 Vdc; drive a minimum of 2,000 Ohms
• 4-20 mA; drive a maximum of 600 Ohms
• Electronic Series 90
• Floating
38

Advertisement

loading

This manual is also suitable for:

T775u2006T775u2016