Setup Procedure
The Setup process uses a hierarchical menu structure
that is easy to use. You press the t and u arrow buttons to
move forward and backward through the menus.
NOTE: The menus can display only those relays that
are defined in Setup (see "1.3.2. NBR OF
RELAYS" on page 22). For example, if you
configure only two relays, then only two
relays display on the appropriate menus.
SETUP
SENSORS
Fig. 25. Setup - Sensors Menu.
SETUP
SENSORS
# SENSORS
Fig. 26. Setup - Sensors - Number of Sensors.
SETUP
SENSORS
SENSOR A
Fig. 27. Setup - Sensors - Sensor A Menu.
SETUP
SENSORS
# SENSORS
SENSOR A
SENSOR B
EXIT
SETUP
SENSORS
# SENSORS
2
ENTER
NUMBER OF
SENSORS
SENSOR A
SENSOR A
TYPE = 0-5V, 0-10V,
TYPE = PT1000
OR 4-20MA
SETUP
SETUP
SENSORS
SENSORS
SENSOR A
SENSOR A
TYPE
TYPE
UNITS
UNITS
CALIBRATE
MIN VAL
LABEL
MAX VAL
EXIT
CALIBRATE
LABEL
EXIT
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
To change the controller's sensors and output setup
parameters, perform the following procedures in the order
listed:
1. Enter Setup mode — see "1.1. Entering Setup
Mode"
2. Setup Sensors — see "1.2. Setting up the Sensors"
3. Setup Outputs — see "1.3. Setting up the Outputs"
on page 18
4. Exit Setup Mode — see "1.4. Exiting Setup" on
page 26
1.1. Entering Setup Mode
To enter Setup mode, press and hold the MENU button for
five seconds to display the Setup menu. See Fig. 24 on
page 13.
1.2. Setting up the Sensors
1. From the Setup menu, use the p and q buttons to
highlight SENSORS.
2. Press the u button to display the Sensors menu.
M24586
1.2.1. Number of SENSORS
The value entered here determines the number of
sensors displayed on the home screen.
NOTE: For applications that do not use Reset, only
one sensor (Sensor A) is available for use.
1. From the Sensors menu, highlight # SENSORS then
press the u button to display the number of sensors.
2. Use the p and q buttons to enter the number of sen-
sors (1 or 2).
Default: 2
M24587
3. Press the u button to accept the value and display
the SENSOR A selection.
1.2.2. SENSOR A
If you are implementing two-sensor reset control, Sensor A
must always be the controlled temperature and Sensor B must
always be the controlling temperature. For example, in a reset
control based on outside temperature, Sensor A must be the
inside sensor and Sensor B must be the outside sensor.
1. From the Sensors menu, highlight SENSOR A.
2. Press the u button to display the Sensor A selec-
tions.
The menu selections change depending on whether the
sensor type is 1097 PTC (temperature) or 0-10V / 4-
20MA.
M24588A
15
62-0255—09