SAFETY MANUAL SIL KFD2-UT2-(EX)*, HID2082
Proof Test
Additionally the loop diagnosis shall be tested to prove that the fault signalling via
the current output is working correctly. The output current in the event of a failure
depends on the device configuration. Please record this configuration and the
resulting expected fault signalling current in the test report. Example: if downscale
is configured, 2.0 mA ±1 % must be measured in the event of a failure. The red
LED must be blinking.
Thermocouple:
Disconnect simulator (lead breakage).
Disconnect fixed resistor (lead breakage of CJC).
Apply short circuit between terminal 2 and 3 for channel I and between
terminals 5 and 6 for channel II (short circuit of CJC).