El3312 - Connection - Beckhoff EL33-00 Series Documentation

Analog thermocouple input terminal (open-circuit recognition, 1, 2, 4 ch.)
Table of Contents

Advertisement

4.13.2

EL3312 - Connection

Fig. 49: EL3312
Earthed thermocouples
Observe for earthed thermocouples: Differential inputs max. ± 2 V to ground!
Current carrying capacity of the input contacts
The maximum permitted current on the signal-relevant terminal points (inputs, GND) is 40 mA (if ap-
plicable).
EL3312 - Connection
Terminal point No.
Input +TC1
1
Input  +TC2
2
GND
3
Shield
4
Input -TC1
5
Input  -TC2
6
GND
7
Shield
8
EL33xx-00x0
Comment
Input +TC1
Input +TC2
Ground (internally connected with terminal point 7)
Shield (internally connected to terminal point 8)
Input -TC1
Input -TC2
Ground (internally connected with terminal point 3)
Shield (internally connected to terminal point 4)
Version: 4.2
Mounting and wiring
65

Hide quick links:

Advertisement

Table of Contents
loading