Configuration Data - Beckhoff EL33-00 Series Documentation

Analog thermocouple input terminal (open-circuit recognition, 1, 2, 4 ch.)
Table of Contents

Advertisement

5.10.2

Configuration data

Index 80n0 TC Settings  (for Ch. 1 - 8 (0 ≤ n ≤  7))
Index (hex) Name
80n0:0
TC Settings
80n0:01
Enable user
scale [} 152]
80n0:02
Presentation
[} 149]
3)
80n0:05
Siemens bits
[} 149]
80n0:06
Enable filter
[} 150]
2) 3)
80n0:07
Enable limit 1
[} 151]
2) 3)
80n0:08
Enable limit 2
[} 151]
80n0:0A
Enable user cali-
bration [} 152]
80n0:0B
Enable vendor
calibration
[} 151]
80n0:0C
Coldjunction
compensation
[} 154]
80n0:0E
Disable wire
break detection
[} 155]
80n0:11
User scale offset
[} 152]
8000:12
User scale gain
[} 152]
2) 3)
80n0:13
Limit 1 [} 151]
2) 3)
80n0:14
Limit 2 [} 151]
2) 
not EL3318
3)
  not EL3314‑0010
4)
  only EL3314‑0002, EL3314‑0010
EL33xx-00x0
Meaning
Maximum subindex
User scaling is active.
EL331x-0000
0: Signed presentation, 0.1°C/digit
1: Absolute value with MSB as sign (signed amount repre-
sentation), 0.1°C/digit
2: High resolution (0.01°C/digit)
EL3314‑0002, EL3314‑0010
0: 0.1°C/digit
2: 0.01°C/digit (default)
3: 0.001°C/digit
The S5 bits are displayed in the three low-order bits
This setting generally activates the basic filters in object
0x80n0:15. In the EL33xx these are technically realized in
the ADC and can therefore not be switched off, even if they
are set to "disabled" in the object.
Limit 1 enabled
Limit 2 enabled
Enabling of the user calibration
Enabling of the vendor calibration
0: internal
1: no
Cold junction compensation is not active
2: Extern process data
Cold junction compensation takes place via the process data
(resolution [1/10]°C)
0: Wire break detection is active
1: Wire break detection is not active
User scaling offset
User scaling gain.
The gain is represented in fixed-point format, with the factor
-16
2
.
The value 1 corresponds to 65536 (0x00010000)
First limit value for setting the status bits (resolution 0.1 °C)
Second limit value for setting the status bits (resolution 0.1
°C)
Version: 4.2
Commissioning
Data type
Flags Default
UINT8
RO
EL331x-0000:
0x19 (25
EL3314‑0002,
EL3314‑0010:
0x1A (26
BOOLEAN
RW
0x00 (0
BIT3
RW
0x00 (0
BOOLEAN
RW
0x00 (0
BOOLEAN
RW
0x01 (0
BOOLEAN
RW
0x00 (0
BOOLEAN
RW
0x00 (0
BOOLEAN
RW
0x00 (0
BOOLEAN
RW
0x01 (1
BIT2
RW
0x00 (0
BOOLEAN
RW
0x00 (0
INT16
RW
0x0000 (0
INT32
RW
0x00010000
(65536
INT16
RW
0x0000 (0
INT16
RW
0x0000 (0
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec