Positioning Of Passive Terminals; Installation Positions 331X-0000 - Beckhoff EL33-00 Series Documentation

Analog thermocouple input terminal (open-circuit recognition, 1, 2, 4 ch.)
Table of Contents

Advertisement

Mounting and wiring
4.9

Positioning of passive Terminals

Hint for positioning of passive terminals in the bus terminal block
EtherCAT Terminals (ELxxxx / ESxxxx), which do not take an active part in data transfer within the
bus terminal block are so called passive terminals. The passive terminals have no current consump-
tion out of the E-Bus.
To ensure an optimal data transfer, you must not directly string together more than 2 passive termi-
nals!
Examples for positioning of passive terminals (highlighted)
Fig. 36: Correct positioning
Fig. 37: Incorrect positioning
4.10

Installation positions 331x-0000

Constraints regarding installation position and operating temperature range
Please refer to the technical data for a terminal to ascertain whether any restrictions regarding the installa-
tion position and/or the operating temperature range have been specified. When installing high power dissi-
pation terminals ensure that an adequate spacing is maintained between other components above and be-
low the terminal in order to guarantee adequate ventilation!
54
NOTE
Version: 4.2
EL33xx-00x0