Download Print this page

Bosch CP156B Installer's Reference Manual page 5

External metal keypad with smart card reader

Advertisement

The keypad can display alarm and door status at
i
the same time.
Note
LED Operation For Area Control
Led
Condition
On
Red
Flashing
On
Green
Flashing
Red/Green
Alternate
& Blue
Flashing
Red/Green
Both Off
& Blue
Red/Green
Off
Table 5: Keypad LED's - Area Control
To have the keypad control an area on the alarm system
you need to assign the keypad to a home area. See the
Devices-Keypads-Home Area menu option in panel pro-
gramming. If alarm system control is not required then
you should set the home area option to No Area.
To have the keypad control a door on the system you
will need to assign a door to the keypad. See the De-
vices-Keypads-Door Assignment menu option in panel
programming.
LED Function For Door Control
Led
Condition
Blue
On
Blue
Fast Flash
Continuous
Blue
Fast Flash
Blue
2 Flashes
Red/Green
Alternate
& Blue
Flashing
Blue
Off
Bosch Security Systems
01/19 CP156BIRG FTR1.1
Meaning
Area All On or Part On and
no alarm
Area Alarm
Area is OFF
Area not ready to turn on -
zone(s) unsealed
Keypad initialising during
power up or LAN scan.
Home Area and Door As-
signment not programmed
or keypad not powered
or keypad is in extinguish
mode.
Keypad has not been as-
signed to a home area.
Meaning
Door Locked
Door Unlocked
Door manually unlocked
or overridden.
Door automatically un-
locked by time zone
Keypad initialising during
power up or LAN scan.
Door not programmed or
keypad not powered.
CP156B
Table 6: Keypad LED's - Door Control
Once assigned to a door, the on-board Lock output and
Egress input will automatically be assigned to the same
door as the keypad.
If both alarm area and door control is required then
you will need to assign a home area and a door to the
keypad.
The CP156B LED indicators will only display the
i
status of the programmed home area. You can-
Note
not move between areas from this keypad. If you
require multiple area status visibility you should use
a display keypad like the CP700B.
Keypad Alert Tones
The CP156B keypad emits several distinct tones to alert
you to particular system events. The keypad volume lev-
el cannot be adjusted on the CP156B however it can be
turned off via panel programming by setting the keypad
volume to the lowest level. See Devices-Commands-
Volume menu in panel programming.
Setting the keypad volume to off will also stop the
i
key press beep during normal operation.
Note
Keypad Alert Tones
Event
If the system registers a fire alarm, the
reader will sound 3 short beeps fol-
Fire
lowed by a 1.5 second pause. This will
Alarm
repeat until reset by the user or until
the siren run time expires.
If the system registers a burglary
Burglary
alarm, the keypad will sound a con-
Alarm
tinuous siren tone until reset by a user
or until the siren run time expires.
If a system trouble condition occurs,
the keypad will sound 4 x fast short
beeps followed by a 5 second pause
Trouble
and will repeat this tone until the user
acknowledges the trouble
condition from a display keypad
Key
The keypad will sound one short beep
Press
every time a button is pressed.
The exit delay warning will sound 1
short beep every second when the
area the keypad has been assigned to
Exit
is armed. During the last 10
Delay
seconds of exit time the warning tone
will speed up indicating that the time
has nearly expired.
Installer Reference Guide
Alert Tone Emitted
5

Advertisement

loading