Visonic NEXT PIR MCW Installation Instructions Manual

Visonic NEXT PIR MCW Installation Instructions Manual

Wireless, powercode digital pir / pet immmune pir detectors

Advertisement

Quick Links

I
NEXT PIR MCW, NEXT K9-8S MCW
I
GB/US: Lens
SP: Lente
PT: Lente
GB/US: Walk-Test LED
SP: LED de modo de pruebas
PT: LED do teste de passagem
~
Visonia
Fig. 1 - NEXT PIR MCW / NEXT K9-8S MCW
Detectores PIR Digital / Inmune a mascotas inalambricos -
Instrucciones de instalaci6n
Wireless, PowerCode Digital PIR / Pet Immmune PIR
Detectors - Installation Instructions
Detector PIR Digital / Imune a Animais Via radio - Instru<;:6es
de Instala ao
ENGLISH
1.
INTRODUCTION
The NEXT PIR MCW and NEXT K9-85 MCW (pet immune) are
microprocessor-controlled wireless digital PIR detectors.
NEXT is a registered mark of Vi sonic Ltd.
The detectors features are as follows:
• Cylindrical lens with uniform detection sensitivity throughout its
operating range, up to 12 meters (40 ft).
• NEXT PIR MCW includes wall creep zone protection.
• In NEXT K9-85 MCW, Target Specific Imaging™ (TSI) technology is
used for distinction between human beings and pets weighing up to
38 kg (85Ib).
• Incorporates a fully supervised PowerCode transmitter.
• The advanced True Motion Recognition™
algorithm (patented)
allows distinguishing between the true motion of an intruder and any
other disturbances which may cause false alarms.
• Sophisticated frequency domain digital signal processing.
• No vertical adjustment is needed.
• An on-board motion event jumper determines whether 1 or 2
consecutive motion events trigger an alarm.
• After detection, the detector disarms itself to save battery power. It
rearms (reverts to the ready state) if there is no subsequent
detection throughout the following 2-minute period.
• An
optional
version
provides better protection
for systems
compliant with DD243. After initial detection, the detector is
capable of 6 additional detections for a period of 5 minutes.
Further detection is possible only if no movement occurs during the
following 2 minutes. The detector will revert to the initial state if
there is no movement for an additional 5 minutes.
• Very low current consumption.
• Microprocessor-controlled temperature compensation.
• Sealed chamber protects the optical system.
• Front cover tamper switch.
• Back tamper switch (option - NEXT PIR T MCW).
• White light protection.
• Elegantly styled, sturdy case.
For UL installations: The detector is for use with UL listed control
unit PowerMax+ only. Pet immunity has not been evaluated by UL.
2. SPECIFICATIONS
Detector Type: Dual element low-noise pyroelectric sensor
Lens Data
No. of Curtain Beams:
NEXT PIR MCW 9
+
5,
NEXT K9-85 MCW 9
Max. Coverage: 12 x 12 m. (40 x 40 ft) I 90°
Pet Immunity (NEXT K9-85 MCW Only): Up to 38 kg (85 Ib).
ELECTRICAL
Internal Battery: 3V Lithium battery,
type
CR-123A. For UL installations, use
Panasonic or Sanyo only.
Nominal Battery Capacity: 1450 mA/h.
Standby Current Drain: Approx. 0.025 mAo
Transmit Current Drain: 20 mA (including LED).
Battery Life (with LED on): Typically over 3 years.
Battery Power Test: Performed immediately upon battery insertion
and periodically after every several hours.
FUNCTIONAL
True Motion Event Verification: 2 position selector - 1 (OFF) or 2
(ON) motion events.
Alarm Period: 3 seconds.
Visual Indications:
LED Lights for about 3 seconds upon transmission of alarm
&
tamper messages and upon motion detection in the walk test mode.
LED Flashes during the power-up stabilization period, or after
restoring (pressing) the tamper switch.
LED Does not light upon transmission of supervision messages.
Rearm Timer: Rearms the detector 2 minutes after the last alarm.
Timer disabled in the walk test mode - not applicable for the DD243
version (see section 1).
WIRELESS
Frequency (MHz): 315 (U.S. version), 43392, 868.95, 869.2625 or
other frequency according to local requirements.
Transmission Sequence: 3 data bursts at variable intervals within 3
seconds.
Encoding: 24-bit ID, over 16 million possible combinations.
Total Message Length: 36 bits.
Tamper Alert: Reported when a tamper event occurs and in any
subsequent message, until the tamper switch is restored.
Supervision Message: Signaling at 60 minutes interval (U.S. version).
15 minute interval (UK version) or according to local standards.
MOUNTING
Height: 1.8 - 2.4 m (6 - 8 ft). For NEXT K9-85 MCW, the recommended
height is up to 2.1 m (7 ft)
Installation Options: Surface or corner.
ACCESSORIES:
BR-1: Surface mounted swivel bracket, adjustable 30° down and 45°
lefU45° right.
BR-2: BR-1 with a corner adapter
BR-3: BR-1 with a ceiling adapter
ENVIRONMENTAL
RFI Protection: >20
Vim
up to 1000 MHz.
Operating Temperatures: -10°C to 50°C (14°F to 122°F).
Storage Temperatures: -20°C to 60°C (-4°F to 140°F).
Compliance with Standards: Designed to meet FCC Part 15 and Directive
1999151EC of the European Parliament En 50131-1 Grade 2 (detector with back
tamper switch) I Grade 1 (detector without back tamper switch), Class II
Telefication is the certification body for NEXT PIR MCW & NEXT PIR T MCW
PHYSICAL
Size (H x W x D): 94.5 x 63.5 x 53.0 mm (3-11/16 x 2-1/2 x 2-1/16").
Weight (with battery): 70 9 (2.5 oz).
Color: White.
PATENTS: U.S. Patents 5,693,943.6,211,522. D445,709 (another
patent pending).
3. INSTALLATION
3.1 General Guidance
(see fig. 3)
1. Keep away from heat sources.
5. Keep wiring away from power
2. Do not expose to air drafts.
cables.
3. Do not install outdoors.
6. Do not install behind partitions.
4. Avoid direct sunshine.
7. Mount on solid stable surface.
3.2 Installation Procedure
1. Mounting - see fig. 4.
2. Battery installation (see fig. 4)
3. Detector reset:
With
the
battery
in
place,
press
both
tamper
switches
simultaneously (see fig. 4) and release them. The front LED will
flash for about 2 minutes until the detector stabilizes.
Note: The detector transmits a low battery signal upon detection of
low voltage. It is recommended to wait about 1 minute after battery
removal, before inserting the new battery.
4. Enrolling:
Enroll the detector's ID into the alarm system memory according to
the alarm system insallation instructions. When you are instructed
to transmit, press both tamper switches again and release them.
You may enroll the detector's ID while the detector's LED flashes
5. Jumpers settings - see fig. 5.
6. Walk-test the coverage area - see fig. 2. Walk across the far end of
coverage pattern in both directions. The LED should light for 2-3
seconds each time your motion is detected.
Important! Instruct the user to walk test at least once a week to
verify proper function of the detector.
D-3591-EPS
I
NEXT PIR MCW, NEXT K9-8S MCW
I
GB/US: Lens
SP: Lente
PT: Lente
GB/US: Walk-Test LED
SP: LED de modo de pruebas
PT: LED do teste de passagem
~
Visonia
Fig. 1 - NEXT PIR MCW / NEXT K9-8S MCW
Detectores PIR Digital / Inmune a mascotas inalambricos -
Instrucciones de instalaci6n
Wireless, PowerCode Digital PIR / Pet Immmune PIR
Detectors - Installation Instructions
Detector PIR Digital / Imune a Animais Via radio - Instru<;:6es
de Instala ao
ENGLISH
1.
INTRODUCTION
The NEXT PIR MCW and NEXT K9-85 MCW (pet immune) are
microprocessor-controlled wireless digital PIR detectors.
NEXT is a registered mark of Vi sonic Ltd.
The detectors features are as follows:
• Cylindrical lens with uniform detection sensitivity throughout its
operating range, up to 12 meters (40 ft).
• NEXT PIR MCW includes wall creep zone protection.
• In NEXT K9-85 MCW, Target Specific Imaging™ (TSI) technology is
used for distinction between human beings and pets weighing up to
38 kg (85Ib).
• Incorporates a fully supervised PowerCode transmitter.
• The advanced True Motion Recognition™
algorithm (patented)
allows distinguishing between the true motion of an intruder and any
other disturbances which may cause false alarms.
• Sophisticated frequency domain digital signal processing.
• No vertical adjustment is needed.
• An on-board motion event jumper determines whether 1 or 2
consecutive motion events trigger an alarm.
• After detection, the detector disarms itself to save battery power. It
rearms (reverts to the ready state) if there is no subsequent
detection throughout the following 2-minute period.
• An
optional
version
provides better protection
for systems
compliant with DD243. After initial detection, the detector is
capable of 6 additional detections for a period of 5 minutes.
Further detection is possible only if no movement occurs during the
following 2 minutes. The detector will revert to the initial state if
there is no movement for an additional 5 minutes.
• Very low current consumption.
• Microprocessor-controlled temperature compensation.
• Sealed chamber protects the optical system.
• Front cover tamper switch.
• Back tamper switch (option - NEXT PIR T MCW).
• White light protection.
• Elegantly styled, sturdy case.
For UL installations: The detector is for use with UL listed control
unit PowerMax+ only. Pet immunity has not been evaluated by UL.
2. SPECIFICATIONS
Detector Type: Dual element low-noise pyroelectric sensor
Lens Data
No. of Curtain Beams:
NEXT PIR MCW 9
+
5,
NEXT K9-85 MCW 9
Max. Coverage: 12 x 12 m. (40 x 40 ft) I 90°
Pet Immunity (NEXT K9-85 MCW Only): Up to 38 kg (85 Ib).
ELECTRICAL
Internal Battery: 3V Lithium battery,
type
CR-123A. For UL installations, use
Panasonic or Sanyo only.
Nominal Battery Capacity: 1450 mA/h.
Standby Current Drain: Approx. 0.025 mAo
Transmit Current Drain: 20 mA (including LED).
Battery Life (with LED on): Typically over 3 years.
Battery Power Test: Performed immediately upon battery insertion
and periodically after every several hours.
FUNCTIONAL
True Motion Event Verification: 2 position selector - 1 (OFF) or 2
(ON) motion events.
Alarm Period: 3 seconds.
Visual Indications:
LED Lights for about 3 seconds upon transmission of alarm
&
tamper messages and upon motion detection in the walk test mode.
LED Flashes during the power-up stabilization period, or after
restoring (pressing) the tamper switch.
LED Does not light upon transmission of supervision messages.
Rearm Timer: Rearms the detector 2 minutes atter the last alarm.
Timer disabled in the walk test mode - not applicable for the DD243
version (see section 1).
WIRELESS
Frequency (MHz): 315 (U.S. version), 43392, 868.95, 869.2625 or
other frequency according to local requirements.
Transmission Sequence: 3 data bursts at variable intervals within 3
seconds.
Encoding: 24-bit ID, over 16 million possible combinations.
Total Message Length: 36 bits.
Tamper Alert: Reported when a tamper event occurs and in any
subsequent message, until the tamper switch is restored.
Supervision Message: Signaling at 60 minutes interval (U.S. version).
15 minute interval (UK version) or according to local standards.
MOUNTING
Height: 1.8 - 2.4 m (6 - 8 tt). For NEXT K9-85 MCW, the recommended
height is up to 2.1 m (7 tt)
Installation Options: Surface or corner.
ACCESSORIES:
BR-1: Surface mounted swivel bracket, adjustable 30° down and 45°
lefU45° right.
BR-2: BR-1 with a corner adapter
BR-3: BR-1 with a ceiling adapter
ENVIRONMENTAL
RFI Protection: >20
Vim
up to 1000 MHz.
Operating Temperatures: -10°C to 50°C (14°F to 122°F).
Storage Temperatures: -20°C to 60°C (-4°F to 140°F).
Compliance with Standards: Designed to meet FCC Part 15 and Directive
1999151EC of the European Parliament En 50131-1 Grade 2 (detector with back
tamper switch) I Grade 1 (detector without back tamper switch), Class II
Telefication is the certification body for NEXT PIR MCW & NEXT PIR T MCW
PHYSICAL
Size (H x W x D): 94.5 x 63.5 x 53.0 mm (3-11/16 x 2-1/2 x 2-1/16").
Weight (with battery): 70 9 (2.5 oz).
Color: White.
PATENTS: U.S. Patents 5,693,943.6,211,522. D445,709 (another
patent pending).
3. INSTALLATION
3.1 General Guidance
(see fig. 3)
1. Keep away from heat sources.
5. Keep wiring away from power
2. Do not expose to air drafts.
cables.
3. Do not install outdoors.
6. Do not install behind partitions.
4. Avoid direct sunshine.
7. Mount on solid stable surface.
3.2 Installation Procedure
1. Mounting - see fig. 4.
2. Battery installation (see fig. 4)
3. Detector reset:
With
the
battery
in
place,
press
both
tamper
switches
simultaneously (see fig. 4) and release them. The front LED will
flash for about 2 minutes until the detector stabilizes.
Note: The detector transmits a low battery signal upon detection of
low voltage. It is recommended to wait about 1 minute after battery
removal, before inserting the new battery.
4. Enrolling:
Enroll the detector's ID into the alarm system memory according to
the alarm system insallation instructions. When you are instructed
to transmit, press both tamper switches again and release them.
You may enroll the detector's ID while the detector's LED flashes
5. Jumpers settings - see fig. 5.
6. Walk-test the coverage area - see fig. 2. Walk across the far end of
coverage pattern in both directions. The LED should light for 2-3
seconds each time your motion is detected.
Important! Instruct the user to walk test at least once a week to
verify proper function of the detector.