Honeywell T775P 2000 Series Installation Instructions Manual page 30

Electronic stand-alone controller
Table of Contents

Advertisement

T775P SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
PROGRAM
SETPOINT
Fig. 75. Program - Setpoint.
PROGRAM
THROT RNG
Fig. 76. Program - Throttling Range.
PROGRAM
SENSOR
Fig. 77. Program - Sensor Selection.
PROGRAM
HEAT/COOL
Fig. 78. Program - Heat/Cool Selection.
62-0256—11
MENU
PROGRAM
SETPOINT
0
o
F
ENTER
SETPOINT
FOR
STAGES
M24643
MENU
PROGRAM
THROT RNG
20
o
F
ENTER
THROTTLING
RANGE
M24644
MENU
PROGRAM
SENSOR
SENSOR A
SENSOR C
SELECT
SENSOR FOR
STAGES
M24639
MENU
PROGRAM
HEAT/COOL
HEAT
COOL
SELECT
HEAT/COOL
FOR
STAGES
M24640
30
3.1.1. SETPOINT
1. From the menu, use the  and  buttons to high-
light SETPOINT.
2. Press the  button to display the setpoint value.
3. Use the  and  buttons to increase/decrease the
desired setpoint temperature.
Default: 0°F (-18°C)
Range: -40°F to 248°F (-40°C to 120°C)
4. Press the  button to accept the setpoint tempera-
ture and display the next option.
3.1.2. THROTTLING RANGE
The Throttling Range brackets the setpoint setting, e.g., if
the setpoint is 72°F and the throttling range is 10°F, then
the effective throttling temperature range is 67°F to 77°F.
1. From the menu, use the  and  buttons to high-
light THROT RNG.
2. Press the  button to display the throttling range
value.
3. Use the  and  buttons to increase/decrease the
desired value.
Default: 20°F (-6.6°C)
Range: 1°F to 150°F (1°C to 66°C)
4. Press the  button to accept the value and display
the next option.
3.1.3. SENSOR
Select Sensor A to use the Supply sensor as the
controlled temperature.
Select Sensor C to use the Return sensor as the
controlled temperature.
1. From the menu, use the  and  buttons to high-
light SENSOR.
2. Press the  button to display the sensor selections.
3. Use the  and  buttons to select Sensor A or C.
Default: Sensor A
4. Press the  button to accept the highlighted sensor
and display the next option.
3.1.4. HEAT/COOL
1. From the menu, use the  and  buttons to high-
light HEAT/COOL.
Default: HEAT
2. Press the  button to display the heat and cool
selections.
3. Use the  and  buttons to select Heat or Cool.
4. Press the  button to accept the value and display
the next option.

Hide quick links: