Honeywell T775P 2000 Series Installation Instructions Manual page 27

Electronic stand-alone controller
Table of Contents

Advertisement

RESET = YES-OTHER
AND
DI OPTION = SETBACK
MENU
PROGRAM
SP MAX
RESET B1
SP MIN
RESET B2
THROT RNG
SENSOR
HEAT/COOL
SETBACK
EXIT
Fig. 65. Setpoint Values for Reset and Setback.
PROGRAM
SP MAX
Fig. 66. Program - Sensor A - Max. Setpoint.
PROGRAM
R
RESET B1
Fig. 67. Program - Sensor B - Min. Setpoint.
PROGRAM
SP MIN
Fig. 68. Program - Sensor A - Min. Setpoint.
T775P SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
RESET = YES-BOILER
AND
DI OPTION = SETBACK
MENU
PROGRAM
OR
BOILR MAX
OUTSD MIN
BOILR MIN
OUTSD MAX
THROT RNG
SENSOR
HEAT/COOL
SETBACK
EXIT
M24544
MENU
PROGRAM
SP MAX
180
o
F
ENTER
MAXIMUM
SETPOINT
M24576
MENU
PROGRAM
RESET B1
10
o
F
ENTER
MINIMUM
VALUE FOR
OUTSIDE B
M24585
MENU
PROGRAM
SP MIN
140
o
F
ENTER
MINIMUM
SETPOINT
M24636
2.2. Program Menus for Reset
Press the MENU button, then select PROGRAM and
press the  button to view the Program menu.
Fig. 65 shows the menus for Reset-Other and Reset-
Boiler. Your menu is the one chosen in "2.1. Setting Up
the Controller for Reset" on page 26.
NOTE: The Setback parameter displays only if
scheduling is enabled (see Fig. 30 on
page 16) or the DI Option is set to Setback.
(see Fig. 40 on page 19).
2.2.1. SP MAX or BOILER MAX
Setpoint maximum for Sensor A.
1. From the menu, use the  and  buttons to high-
light SP MAX or BOILR MAX.
2. Press the  button to display the maximum setpoint
value.
3. Use the  and  buttons to increase/decrease the
desired maximum setpoint temperature.
Default: 180°F (82°C)
Range: -40°F to 248°F (-40°C to 120°C)
4. Press the  button to accept the setpoint tempera-
ture and display the next option.
2.2.2. RESET B1 or OUTSD MIN
Sensor B value when Sensor A setpoint is at maximum.
1. From the menu, use the  and  buttons to high-
light RESET B1 or OUTSD MIN.
2. Press the  button to display the setpoint value.
3. Use the  and  buttons to increase/decrease the
desired setpoint temperature.
Default: 10°F (-12°C)
Range: -40°F to 248°F (-40°C to 120°C)
4. Press the  button to accept the value and display
the next option.
2.2.3. SP MIN or BOILER MIN
Setpoint minimum for Sensor A.
1. From the menu, use the  and  buttons to high-
light SP MIN or BOILR MIN.
2. Press the  button to display the setpoint value.
3. Use the  and  buttons to increase/decrease the
desired minimum setpoint temperature.
Default: 140°F (60°C)
Range: -40°F to 248°F (-40°C to 120°C)
4. Press the  button to accept the setpoint tempera-
ture and display the next option.
27
62-0256—11