Remove the control
terminals and blank
cover.
Pos : 126 /Anleitungen/El ektr onik /Safety /4. M ontage und Installation/Elek trischer Ansc hl uss _01 @ 15\mod_1485429904375_388.docx @ 2316246 @ 2 @ 1
3.2 Electrical connection
The information for installation or electrical connection from the manual BU 0600 as well as all of the
following information must be observed.
Pos : 127 /Anleitungen/El ektr onik /FU und Starter/1. Allgemei nes /Sic herheits- und Ins tall ations hinw eis e und W arn- Gefahrenhinw eise/Sic herheits hinw eise (auslaufend)/versc hiedene/W ARNUNG - El ektrisc her Sc hlag ( nicht unter Spannung ar beiten) @ 14\m od_1480331381423_388.docx @ 2308485 @ @ 1
WARNING
Touching electrically conducting components may cause an electric shock and severe or possibly fatal injury.
•
Disconnect the frequency inverter from the power supply before starting installation work.
•
Only work on devices which have been disconnected from the power supply.
Pos : 128 /Anleitungen/El ektr onik /FU und Starter/1. Allgemei nes /Sic herheits- und Ins tall ations hinw eis e und W arn- Gefahrenhinw eise/Sic herheits hinw eise (auslaufend)/versc hiedene/W ARNUNG - El ektrisc her Sc hlag (W artez eit) @ 14\mod_1480332099956_388.docx @ 2308520 @ @ 1
WARNING
The frequency inverter carries hazardous voltage for up to 5 minutes after being switched off.
•
Only start work after a waiting period of at least 5 minutes after switching off the mains supply
(disconnection).
Pos : 130 /Anleitungen/El ektr onik /Safety /4. M ontage und Installation/Ver drahtungsric htlini en [BU0630] @ 44\m od_1593153830132_388.doc x @ 2638326 @ 3 @ 1
3.2.1 Wiring guidelines
Wire end sleeves must be used if flexible cables (multiple strand or fine-wire) are used for the
connections X19 (at position X17) or X20. In addition, the wiring guidelines in the frequency inverter
manual (BU 0600) also apply.
Pos : 132 /Anleitungen/El ektr onik /Safety /4. M ontage und Installation/N etz anschl uss [BU0630] @ 40\m od_1578408046098_388.doc x @ 2582167 @ 3 @ 1
3.2.2 Mains connection
Devices for implementation of a safety function must only be operated on TN, TT and IT networks.
Grounded Corner operation is not intended.
For operation in IT networks
•
the IT network screws must be removed
•
a braking resistor must be used
Pos : 133 /Anleitungen/El ektr onik /FU und Starter/1. Allgemei nes /Sic herheits- und Ins tall ations hinw eis e und W arn- Gefahrenhinw eise/neu/War n- und Gefahrenhinw eise/ACHTUN G - Betrieb am IT – Netz [SK 5xxP] @ 32\m od_1553605071546_388.docx @ 2520590 @ @ 1
BU 0630 en-2020
Remove the STO
contact jumper.
3 Assembly and installation
Install the SK CU5-STO
customer unit.
Electric shock
Electric shock
Install the control
terminals and blank
cover.
29