3.2 Electrical connection

The information for installation or electrical connection from the manual BU 0600 as well as all of the
following information must be observed.
Pos : 127 /Anleitungen/El ektr onik /FU und Starter/1. Allgemei nes /Sic herheits- und Ins tall ations hinw eis e und W arn- Gefahrenhinw eise/Sic herheits hinw eise (auslaufend)/versc hiedene/W ARNUNG - El ektrisc her Sc hlag ( nicht unter Spannung ar beiten) @ 14\m od_1480331381423_388.docx @ 2308485 @ @ 1
WARNING
Touching electrically conducting components may cause an electric shock and severe or possibly fatal injury.
Disconnect the frequency inverter from the power supply before starting installation work.
Only work on devices which have been disconnected from the power supply.
Pos : 128 /Anleitungen/El ektr onik /FU und Starter/1. Allgemei nes /Sic herheits- und Ins tall ations hinw eis e und W arn- Gefahrenhinw eise/Sic herheits hinw eise (auslaufend)/versc hiedene/W ARNUNG - El ektrisc her Sc hlag (W artez eit) @ 14\mod_1480332099956_388.docx @ 2308520 @ @ 1
WARNING
The frequency inverter carries hazardous voltage for up to 5 minutes after being switched off.
Only start work after a waiting period of at least 5 minutes after switching off the mains supply
(disconnection).
Pos : 130 /Anleitungen/El ektr onik /Safety /4. M ontage und Installation/Ver drahtungsric htlini en [BU0630] @ 44\m od_1593153830132_388.doc x @ 2638326 @ 3 @ 1

3.2.1 Wiring guidelines

Wire end sleeves must be used if flexible cables (multiple strand or fine-wire) are used for the
connections X19 (at position X17) or X20. In addition, the wiring guidelines in the frequency inverter
manual (BU 0600) also apply.
Pos : 132 /Anleitungen/El ektr onik /Safety /4. M ontage und Installation/N etz anschl uss [BU0630] @ 40\m od_1578408046098_388.doc x @ 2582167 @ 3 @ 1

3.2.2 Mains connection

Devices for implementation of a safety function must only be operated on TN, TT and IT networks.
Grounded Corner operation is not intended.
For operation in IT networks
the IT network screws must be removed
a braking resistor must be used
Pos : 133 /Anleitungen/El ektr onik /FU und Starter/1. Allgemei nes /Sic herheits- und Ins tall ations hinw eis e und W arn- Gefahrenhinw eise/neu/War n- und Gefahrenhinw eise/ACHTUN G - Betrieb am IT – Netz [SK 5xxP] @ 32\m od_1553605071546_388.docx @ 2520590 @ @ 1
BU 0630 en-2020
Remove the STO
contact jumper.
3 Assembly and installation
Install the SK CU5-STO
customer unit.
Electric shock
Electric shock
Install the control
terminals and blank
cover.