Fire-Lite UDACT-F Instruction Manual page 30

Universal digital alarm communicator / transmitter
Table of Contents

Advertisement

Programming Options

Enter the remaining numbers in their respective addresses as shown below:
4
8
4
7
26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41
Valid entries for both the primary and secondary phone numbers are 0 - F with the numeric digits as dialed numbers
and the alpha digits (A - F) representing the following functions:
A = * on a Touchtone phone keypad
B = # on a Touchtone phone keypad
C = look for secondary dial tone for up to two seconds, then dial anyway
D = three second pause
E = five second pause
F = end of phone number (F must be entered)
Secondary Number Communication Format (42)
One location is needed to select the Communication Format to the secondary phone number. Address 42 is used for
this purpose. The default (factory setting) for this address is 42_A, which is 4+2 Standard, 1800 Hz 'Carrier', 2300
Hz 'ack'. The user may enter 0, 1, 2, 4, 6, 8, C or E in place of the default, then press the [ENTER/STORE] key.
Choose from the list of formats below:
0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: Not used
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: Not used
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: Not used
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: Not used
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: Not used
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: Not used
E: Ademco Contact ID
F: Not used
Note: Consult the Central Station for proper selection or consult the factory representatives. For any format chosen, the UDACT-F
automatically programs all of the event codes. Refer to Table 3-2 on page 34, Table 3-3 on page 35, Table 3-4 on page 36, Table 3-5
on page 37, Table 3-6 on page 38 and Table 3-7 on page 39.
Secondary Number Account Code (43-46)
Four locations at addresses 43 - 46 default to all '0s'. Valid entries are 0 - 9 and A - F. The number of digits entered
must match the format selection. If programming '2' or '4' into address 42, enter three digits (location 46 is ignored).
If programming '0, 1, 6, 8, A, C or E' into address 42, enter four digits.
30
1
6
1
F
F
F
F
Document #50049
F
F
F
F
F
Rev.E0
1/22/01
P/N 50049:E0