UL Power-limited Wiring Requirements

2.3
UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25" away from any nonpower-limited circuit wiring. Furthermore, all power-limited
circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or
conduits. A typical wiring diagram for the UDACT-F is shown below.
Typical Wiring Diagram for UL Power-limited Requirements
FIGURE 2-8:
Use power-limited source
Use power-limited source
23
Document #50049
Rev. E0
01/22/01
P/N 50049:E0