Primary Number Communication Format (16)
One location is needed to select the Communication Format to the primary phone number. Address 16 is used for this
purpose. The default (factory setting) for this address is 16_A, which is 4+2 Standard, 1800 Hz 'Carrier', 2300 Hz
'ack'. The user may enter 0, 1, 2, 4, 6, 8, C or E in place of the default, then press the [ENTER/STORE] key. Choose
from the list of formats below:
0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: Not used
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: Not used
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: Not used
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: Not used
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: Not used
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: Not used
E: Ademco Contact ID
F: Not used
Note: Consult the Central Station for proper selection or consult the factory representatives. For any format chosen, the UDACT-F
automatically programs all of the event codes. Refer to Table 3-2 on page 34, Table 3-3 on page 35, Table 3-4 on page 36, Table 3-5
on page 37, Table 3-6 on page 38 and Table 3-7 on page 39.
Primary Number Account Code (17-20)
The Account Code if provided by the Central Station. Four locations at addresses 17 - 20 which default to all '0s'
must be changed to the supplied Account Code. Valid entries are 0 - 9 and A - F. The number of digits entered must
match the format selection. If programming '2' or '4' into address 16, enter the three digit code (location 20 is
ignored). If programming '0, 1, 6, 8, A, C or E' into address 16, enter the four digit code.
Primary Number 24 Hour Test Time (21-24)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 1 takes up four loca-
tions (addresses 21 - 24). The default is 00:00 (12:00 midnight). The limits for each location are as follows:
21 = 0 to 2
22 = 0 to 9
23 = 0 to 5
24 = 0 to 9
Do not use 'A - F' as entries in these addresses.
Primary Number 24/12 Hour Test Time Interval (25)
The test report sent to the primary phone number may be sent every 12 or 24 hours. If the message is to be sent every
24 hours, leave the factory default entry of '0'. If a 12 hour test report time is needed, enter '1' for 12 hours.
Secondary Phone Number (26-41)
The sixteen addresses are factory set to 'F' (from 26_F to 41_F). Programming is typically done as follows:

If the phone number to be entered is 484-7161, press 4

The display will read 26_4

Press the [ENTER/STORE] key to save the entry to memory and increment to the next address 27_F