Output Circuits
Monitoring for UDACT-F Trouble
FIGURE 2-11:
SLC Loop to Fire
Alarm Control Panel
All wiring to relay must be in the same room
within 20 feet of the UDACT-F and in conduit.
Earth Grnd
Comm Fail
+24 VDC
UDACT-F
Note: MMF-300 Series Monitor Module is used to supervise Normally Closed output of MR-101/C. On UDACT-F trouble and Comm. Fail, MR-101/
C relay contact will open, causing M300 to transmit trouble condition to the FACP .
26
MMF-300 Series
Monitor Module
MR-101/C
(MR-201/C may also be used)
Document #50049
Rev.E0
1/22/01
3.9K ohm EOL
resistor
(supplied)
P/N 50049:E0
Wiring in
same room as
UDACT-F