Section 4
IEC 60870-5-103 vendor specific implementation
4.3.2
40
to the master. A file that has been transferred and acknowledged by the master
cannot be transferred again.
The binary signals that are reported by polling are those that are connected to
the disturbance function blocks B1RBDR to B6RBDR. These function blocks
include the function type and the information number for each signal. For
more information on the description of the Disturbance report in the Technical
reference manual. The analog channels, that are reported, are those connected
to the disturbance function blocks A1RADR to A4RADR. The eight first ones
belong to the public range and the remaining ones to the private range.
The following elements are used in the ASDUs (Application Service Data Units)
defined in the standard.
Analog signals, 40-channels: the channel number for each channel has to be
specified. Channels used in the public range are 1 to 8 and with:
I
connected to channel 1 on disturbance function block A1RADR
L1
I
connected to channel 2 on disturbance function block A1RADR
L2
I
connected to channel 3 on disturbance function block A1RADR
L3
I
connected to channel 4 on disturbance function block A1RADR
N
V
connected to channel 5 on disturbance function block A1RADR
L1E
V
connected to channel 6 on disturbance function block A1RADR
L2E
V
connected to channel 7 on disturbance function block A1RADR
L3E
V
connected to channel 8 on disturbance function block A1RADR
EN
Channel number used for the remaining 32 analog signals are numbers in the
private range 64 to 95.
Binary signals, 96-channels: for each channel the user can specify a FUNCTION
TYPE and an INFORMATION NUMBER.

Deviations from the standard

For each input of the Disturbance recorder function there is a setting for the
information number of the connected signal. The information number can be set to
any value between 0 and 255. Default value is 0.
Furthermore, there is a setting on each input of the Disturbance recorder function
for the function type.
Disturbance upload
All analog and binary signals that are recorded with disturbance recorder can be
reported to the master. The last eight disturbances that are recorded are available
for transfer to the master. A successfully transferred disturbance (acknowledged by
the master) will not be reported to the master again.
1MRS757203 A
630 series
Communication Protocol Manual