Function Commands Generic For Iec 60870-5-103 I103Gencmd; Functionality; Function Block; Signals - ABB Relion 630 Series Communication Protocol Manual

Hide thumbs Also See for Relion 630 Series:
Table of Contents

Advertisement

1MRS757203 A
4.2.4
4.2.4.1
4.2.4.2
4.2.4.3
630 series
Communication Protocol Manual
IEC 60870-5-103 vendor specific implementation
Function type for each function block instance in private range is selected with
parameter FunctionType. Default values are defined in private range 1 - 4. One for
each instance.
Information number must be selected for each output signal. Default values are 1 - 8.
Info. no.
Message
1
Output signal 01
2
Output signal 02
3
Output signal 03
4
Output signal 04
5
Output signal 05
6
Output signal 06
7
Output signal 07
8
Output signal 08
Function commands generic for IEC 60870-5-103
I103GENCMD

Functionality

I103GENCMD is used for transmitting generic commands over IEC 60870-5-103.
The function has two outputs signals CMD_OFF and CMD_ON that can be used to
implement double-point command schemes.

Function block

I103GENCMD
BLOCK
^CMD_OFF
^CMD_ON
IEC10000285-1-en.vsd
IEC10000285 V1 EN
Figure 16:
I103GENCMD function block

Signals

Table 35:
I103GENCMD Input signals
Name
Type
BLOCK
BOOLEAN
Table 36:
I103GENCMD Output signals
Name
Type
CMD_OFF
BOOLEAN
CMD_ON
BOOLEAN
Supported
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Default
Description
0
Block of command
Description
Command output OFF
Command output ON