Considerations For Connecting The Battery System To Operating Equipment - EnerSys PowerSafe mP Series Battery Safety, Installation, Storage, Operating And Maintenance Manual

Vrla battery system
Table of Contents

Advertisement

CONSIDERATION
Ventilation
Grounding
Floor
Anchoring
Proximity to Electronic
Equipment
Cell Identification/
Numbering

5.2 Considerations for Connecting the Battery System to Operating Equipment

The battery has been sized based on a specific load (amps or KW) for a specific run time,
temperature and end voltage. Consult with the system/equipment supplier to determine these
parameters. Battery performance is based on these values which are measured
at the battery terminals.
It is important to ensure that the load cables:
between the battery and its load are the shortest routing possible to the terminal,
allowing sufficient additional cable (about 6" [15 cm]) for connect/disconnect.
are the proper size to minimize the voltage drop between the battery output terminals
and the load.
are connected to the terminal plate (NEVER connect the load cable(s) directly to the
battery terminal).
12
TABLE 5.1 (continued)
No seperate battery room or "hood" exhaust is required. However,
VRL batteries do require adequate ventilation and should not be
installed in "air tight" locations.
It is recommended that the modules or racks be grounded in
accordance with NEC and/or local codes.
Reasonably level. Shimming up to 1/4" (6mm) maximum to level
battery front to rear and side to side. Capable of supporting the
weight of the battery as well as any auxiliary equipment.
All installations should be floor anchored. nchoring should meet all
local, state, federal codes and industry standards.
Floor anchoring and its design are the responsibility of the installer.
Ensure seismic requirements are considered.
®
PowerSafe
VRL batteries may be installed next to electronic
equipment, unless the equipment generates heat.
EnerSys
®
recommends battery one (1) be at the positive (+) output.
Then label the cells in ascending sequential order as the cells are
connected in series. The cells at the end or last cell should be the
highest numbered cell and be at the negative (-) output.
www.enersys.com
RECOMMENDATION
Publication No. US-MP-OM-001
March 2017