  • Page 1 Installation, Operations and Maintenance Instructions Publication No: EN-VX-IOM-001 February 03...
  • Page 2: Table Of Contents

    It is advisable to unpack the monoblocs ascertain if any are missing or damaged. and accessories before commencing In this event contact your Enersys assembly and erection and not to unpack representative. and erect monobloc by monobloc.
  • Page 3: Storage

    Installation terminals. These are factory fitted and there is no need to remove Install batteries in a clean and dry area. PowerSafe VX products them until access to the terminals is required. release minimal amounts of gas during normal operation (gas recombination efficiency ≥...
  • Page 4: Cell Strings Connected In Parallel

    Open circuit voltage variation with temperature is 2.5mV per 10°C. 25°C 2.25-2.28V Discharging 30°C 2.24-2.27V PowerSafe VX batteries must not be left in a discharged condition 35°C 2.22-2.25V after supplying the load but must immediately be returned to float 40°C 2.21-2.24V recharge mode.
  • Page 5 10°C rise in temperature. value and a recharging voltage value according to the temperature ranges indicated in the table below: Maintenance/Checks PowerSafe VX are maintenance free, sealed, lead acid batteries Temperature Float Voltage Recharging Voltage and need no water addition.
  • Page 6: Technical Specifications Of Bloc

    Technical specifications of bloc Type Length Width Height Cell Weight Centres (kg) 8VX100F 12VX100F All dimensions in millimetres Typical connection assembly Item No. Description Cat No. Fastener set M6 Inter-unit connector SUB5176 Inter-tier connector (35 mm max.) Insulating terminal cover SPH0571B Typical assembly drawing www.enersysinc.com...
  • Page 7: Battery Record Sheet

    Battery record sheet Works Order No: Customer Ref: Installed At: Battery Type: No. of Monoblocs: Date Installed: Battery Float Voltage: Ambient Temperature: °C Battery Charging Current: Average Vpc: Comments: Engineer in Charge: Date of Service: Volts Volts Volts Volts Volts Volts Volts Volts...