It is advisable to unpack the monoblocs ascertain if any are missing or damaged. and accessories before commencing In this event contact your Enersys assembly and erection and not to unpack representative. and erect monobloc by monobloc.
Installation terminals. These are factory fitted and there is no need to remove Install batteries in a clean and dry area. PowerSafe VX products them until access to the terminals is required. release minimal amounts of gas during normal operation (gas recombination efficiency ≥...
Open circuit voltage variation with temperature is 2.5mV per 10°C. 25°C 2.25-2.28V Discharging 30°C 2.24-2.27V PowerSafe VX batteries must not be left in a discharged condition 35°C 2.22-2.25V after supplying the load but must immediately be returned to float 40°C 2.21-2.24V recharge mode.
Page 5
10°C rise in temperature. value and a recharging voltage value according to the temperature ranges indicated in the table below: Maintenance/Checks PowerSafe VX are maintenance free, sealed, lead acid batteries Temperature Float Voltage Recharging Voltage and need no water addition.
Battery record sheet Works Order No: Customer Ref: Installed At: Battery Type: No. of Monoblocs: Date Installed: Battery Float Voltage: Ambient Temperature: °C Battery Charging Current: Average Vpc: Comments: Engineer in Charge: Date of Service: Volts Volts Volts Volts Volts Volts Volts Volts...