4. Connect battery cables, AC output power cables, fire protection cables and generator Start/Stop
cables.
Neutral cables
Battery cables
Port Description
AC input
Battery input
PE
Safe grounding
Bolt Specifications
M12
M10
M12
M6
7
PE cables
IT and smart cooling product output power
cables
Lighting cables
Fire Protection and Generator
Start/Stop Cables (ATS input cabinet)
Route a neutral wire from the middle of the
positive and negative battery strings.
Take a battery string consisting of 40 batteries
as an example. A neutral wire is routed from the
middle of positive and negative battery strings,
each consisting of 20 batteries.
Bolt Length
45 mm
30 mm
45 mm
16 mm
Torque
46 N· m
26 N· m
46 N· m
4.5 N· m