Lifebreath 350DCS Operation And Installation Manual page 15

Commercial double core heat recovery system
Table of Contents

Advertisement

Optional Lifebreath Wireless Repeater - Part #99-RX02
Installation and Pairing of Wireless Repeaters: 99-RX02
The RX02 Repeaters are to be plugged directly into a 120V power outlet.
1.
Turn on the main wall control by pressing the ON/OFF button
2.
Press the left and right buttons simultaneously on the main wall control (
main control). The bottom row of 3 LED's will begin flashing. This indicates that the main control is now in pairing mode.
3.
The RX02 Repeater must be powered within 16" of the main wall control for pairing. If an outlet is not available an extension
cord should be used to power the repeater initially for pairing.
4.
Plug the RX02 Repeater into the power outlet. The green light will flash after approximately 12 seconds indicating that the
repeater is paired with the main wall control.
5.
Press the ON/OFF button on the main wall control to exit pairing mode and the Repeater may now be
unplugged and moved to its permanent location.
To pair additional RX02 Repeaters with the same wall control, repeat steps 1-5 until all Repeaters
have been paired.
When installed in its permanent location, the green LED will remain solid to indicate the best
location and the Repeater can be moved farther if required. The green LED will flash to indicate it
is in a good location. A red light indicates the Repeater is out of range and needs to be moved
closer to the main wall control.
NOTE: Wireless Repeaters cannot be used in a network to extend the range of another Wireless
Repeater.
Optional Lifebreath 20/40/60 Minute Timer - Part #99-DET01
Operating your Lifebreath 20/40/60 Minute Fan
Timer Press and release the Select Button to activate a 20,
40 or 60 minute high speed override cycle. The High Speed
Status Light will illuminate and the unit will run on high
speed ventilation for the selected time.
The High Speed Status Light will dim after 10 seconds of run
time.
The High Speed Status Light will flash during the last 5
minutes of the cycle.
The timer connected to the unit will illuminate for the
duration of the override when the Select Button is pressed.
Lockout Mode
Lockout Mode is useful if you wish to disable the timers.
The timer can be set to lockout mode by pressing and
holding the Select Button for five seconds. After five seconds,
the High Speed Status Light will flash; release the Select
Button. The timer is now in lockout mode. If the Select
Button is pressed during lockout mode the High Speed Status
Light will momentarily illuminate but no override will be
initiated.
If lockout mode is initiated when the timer is activated, the
timer will continue its timed sequence but will not allow any
further overrides to be initiated. Lockout mode can be
unlocked by pressing and holding the Select Button for five
seconds. After five seconds the High Speed Status Light will
stop flashing. Release the Select Button and the timer will
now operate normally.
.
and either
High Speed
Status Lights
Select Button
initiates high
speed ventilation
for 20, 40 or 60
minutes.
NOTE ABOUT TIMERS
• Timers mount in standard 2" x 4" electrical boxes.
• Wire multiple timers individually back to the unit.
• Use 3/20 low voltage wire
Red #3
Yellow #4
Green #5
Terminal Block Connections
(from Timer to Terminal Block)
Yellow on timer to YELLOW #4
Red on timer to RED #3
Green on timer to GREEN #5
16
or
buttons, depending on the
RX02
Repeater
Yellow
Red
Green
Power
Plug