Configuring IOEM/REM expansion modules

Quick Start - REM Configuration

An REM has 4 relay outputs. REM relays are available at all 5X00 instrument
menus including sensor, aux, E-Aux, Timer and system menus.

Use AquaManager to configure REM

1.
Verify latest AquaManager version is installed - page 81;
2.
Build AquaManager Network;
Note:
- At AquaManager Help>Contents tab> Working with nodes>Insert Node
with direct connection or Insert Node with IP connection>Insert Slave
device help topic bookmark for information.
3.
for all networked nodes including REM node(s).
4.
Verify latest REM firmware is installed - page 60;
5.
Configure REM node systems management window.
6.
. to upload REM configuration to AquaManager network.
REM systems management window

Configure REM relay(s) to 5X00 system(s)

1.
Follow steps 1-6 of hardware installation-starting on page 25;
2.
Wire REM relays - page 40;
3.
Verify all steps at Use AquaManager to configure REM - page 80 are
completed;
4.
Open AquaManager>open 5X00 node window>
IOEM/REM Safey and Installation Guide
;
80
Configuring IOEM/REM expansion modules
Select 5X00 system tab to be configured;
5.
Configure 5X00 system fields.
6.
Notes:
- At AquaManager Help>Contents tab>Working with nodes>Expansion
modules>REM>Configure REM relay to a 5X00 system bookmark for
information;
to upload system configuration to networked instrument;
7.
Test configured relay output functionality after reconfiguring - see Chapter
8.
4 5X00 instrument manuals Configuring>Sensor Setup>Service> Output
test system menu to verify 4/20mA output.
Notes:
- At Run Screen 5X00 instrument system using REM relay will show control
and or alarm relay icons when REM system relay is energized;
- REM relay events are stored at the 5X00 instrument using the relay;
- REM channels can be assigned to multiple system;

Reset REM to factory

Follow the steps below to reset an REM expansion board back to factory settings.
A factory reset will return all REM channels to the default instrument and channel
names. It is important that AquaManager poll all nodes after any instrument on a
network is reset to factory.
1.
Open front panel - page 32
2.
Press Reset button for about 10 seconds. The reset button located to the
left of the DC power connection (located at location A) on the metal plate
inside the enclosure. Observe that both status leds, as described at page
85, display solid green at the same time before releasing the reset button
3.
Close front panel -page 32.
4.
Poll all nodes at AquaManager to ensure the AquaManager database is
properly updated to reset configurations.
Reconfigure 5X00 system REM outputs after polling all nodes at Aqua-
5.
Manager.
Test configured output functionality after reconfiguring.
6.

Confirm latest AquaManager version is installed on PC

For proper AquaManager functionality it is important that the latest AquaMan-
ager version be installed on your PC. Comprehensive information is provided in
AquaManager Help>Contents tab>Getting Started>System Requirements>Update
AquaManager Software for version information.
IOEM/REM Safey and Installation Guide
81

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ysi remYsi ioem-4Ysi ioem-8

Table of Contents