Preparation

Step 1.1 Choosing the installation
location
If using a multi system, install as described in the
installation manual supplied with the outdoor unit.
Overview of installation location requirements
125 mm
or more
Drain hose hole
You can select the direction of
draining (left or right).
Make at least one round to
reduce noise and vibration.
The actual units may look different from
the images depicted here.
Model
Minimum Maximum
**09*******
3
**12*******
**18*******
3
**24*******
Outdoor Unit
Outer wall
Indoor Unit
Cut insulation to have
rainwater drained
8 English
100 mm or more
125 mm
or more
Maximum pipe height
Maximum
pipe length
(Unit : m)
Pipe length
Pipe height
Standard for
Maximum
factory charge
15
5
8
30
5
15
Make a U-trap (A) on the pipe
(which is connected to the indoor
CAUTION
unit) at outer wall and cut the
bottom part of the insulation
(about 10 mm) to prevent
rainwater from getting inside
through the insulation.
CAUTION
• Comply with the length and height limits
described in the figure above.
• For the product that uses the R-32 refrigerant,
Install the indoor unit on the wall 1.8 m or higher
from the floor.
Minimum clearances for the outdoor unit
Minimum clearance in mm
600
Air flow direction
Top view
When installing 1 outdoor unit
150
600
300
Wall
Side view
(6 cases)
(Unit: mm)
2000