Mitsubishi Electric PEA-RP200WKA Service Manual page 43

Split-type, heat pump air conditioners
Hide thumbs Also See for PEA-RP200WKA:
Table of Contents

Advertisement

7. Reactor, fan, and fan motor (bottom side maintenance)
1. Remove the control box cover according to the
procedure in section 1.
2. Removing the fan motor and ACL cable
(1) Disconnect the connector (CNCT1) from the INV
board and connector (CNACL) from the noise fil-
ter board. Then, disconnect the relay connector.
(2) Remove the cable through the rubber bush.
3. Removing the bottom plate
(1) Remove the ten fixing screws on the bottom plate
(R) to remove it.
4. Removing the reactor
(1) Remove the two fixing screws on the reactor
base (S) to remove it.
5. Removing the fan case
(1) Remove the eight fixing screws on the fan
case (T) to remove it.
6. Removing the fan and fan motor
(1) Remove the two fixing screws and attachment
on the fan motor (U).
(2) Pull out the fan motor in the direction of the
arrow.
Exercise caution when removing heavy parts.
(R)
Fig. 14
(S)
Fig. 15
(T)
Fig. 16
(U)
Fig. 17
41
Noise filter board
INV board

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pea-rp250wka

Table of Contents