(3) Troubleshooting when the main power breaker trips
Check items
[1]
Check the resistance between the terminals
of power supply terminal block TB2 with an
ohmmeter.
Turn the power back on and check again.
[2]
[3]
Check the indoor unit for normal operation.
Symptoms
1 0 to several ohms, or insulation
resistance failure
1 Main power breaker is tripped.
2 Nothing appears on the remote
controller.
1 The indoor unit operates
normally without tripping the
main breaker.
2 Main power breaker is tripped.
32
Actions to take
Check the components in the main inverter
circuit.
*Refer to "(4) Simple check on the main inverter
circuit components".
a. Diode bridge
b. Inrush current limiting resistor
c. AC reactor (ACL)
d. Current sensor (ACCT)
a. Look for a possible short-circuit, and if
found, repair.
b. If no problems are found with item "a," there
may be problems with the fan motor.
The fan motor may have had a ground fault.
See section (2)-[1].