3. Thermistor (Condenser/evaporator) (Liquid pipe)
1. Remove the control box cover according to the
procedure in section 1.
2. Removing the maintenance cover
(1) Remove the ten fixing screws on the cover
(D), cover (E), and cover (F) to remove the
maintenance cover.
3. Removing the thermistor
(1) Disconnect the thermistor connector (CN44) from
the Indoor controller board.
(2) Remove the thermistor (G) from the thermistor
holder (H) on the copper tube.
Thermistor size
Liquid pipe: ø8 mm
Condenser/evaporator: ø6 mm
Exercise caution when removing heavy parts.
Fig. 4
Indoor controller board
Fig. 5
37
,
-
.
G), H)