Bock Water heaters 150 Installation, Operation & Maintenance Instructions Manual

Gas, oil & dual fuel water heaters

Advertisement

Quick Links

TO THE INSTALLER:
Please attach these
instructions next to
the water heater.
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
GAS, OIL & DUAL FUEL WATER HEATERS
WARNING: Improper installation, adjustment, alteration,
service or maintenance can cause serious injury or proper-
ty damage. Refer to this manual. For assistance or addi-
tional information, consult a qualified installer or service
agency.
WARNING: If the information in these instructions is not
followed exactly, fire or explosion may result and can cause
property damage, personal injury or death.
DO NOT INSTALL THE WATER HEATER ON COM-
BUSTIBLE FLOORING. Install in accordance with all local
codes. In the absence of local codes, refer to NFPA 31 or
ANSI Z21.10.1, or contact Bock Water Heaters with
questions concerning proper flooring materials.
Minimum clearance to combustible construction is:
SIDES 6"; BACK 6"; FRONT 24". The installation of
this water heater must conform with local codes and
ordinances. In the absence of local codes, the installa-
tion must comply with the National Fire Protection
Association (NFPA 31) Code.
WARNING: The recommended temperature for normal res-
idential use is 120°F. The dial on the aquastat does not
110 S. Dickinson St. • P.O. Box 8632 • Madison, WI 53708-8632
Phone: 608/257-2225 • Fax: 608/257-5304 • www.bockwaterheaters.com
150 • 200 • 250
Warranty and registration card included
Bock Water Heaters, Inc.
always reflect the outcoming water temperature, which
could occasionally exceed 120°F. The variation in outcom-
ing temperature could be based on factors including but not
limited to usage patterns and type of installation. Test your
water at the tap nearest to the water heater.
WARNING: Hotter water increases the risk of scald injury.
Before changing the temperature setting, read the instruc-
tion manual. Temperatures at which injury occurs vary with
the individual's age and length of exposure.
The slower reaction times of children, elderly and physically
or mentally impaired persons increases the scalding hazard
to them. It is recommended lower water temperatures be
used where these situations exist.
To lower water temperature use point-of-use tempera-
ture limiting devices.
WARNING: Flammable vapors may be drawn to this water
heater from other areas of the structure by air currents. Do
not store or use any flammable liquids in the vicinity of
this heater.
WARNING: Water heater blankets may restrict air flow to
the heater and cause fire, asphyxiation, personal injury or
death.
WARNING: Hydrogen gas can be produced in a hot water
system that had not been used for an extended period-gen-
erally, two weeks or longer. To prevent possible injury
under this situation, we recommend that a hot water faucet
be wide open for several minutes before you use ANY elec-
trical appliance that is connected to the hot water system.
If hydrogen is present, an unusual sound – such as air
escaping – will come from the open faucet as the hot water
begins to flow. Hydrogen gas is extremely flammable –
there must be no open flame near this open faucet.
TO THE CONSUMER:
Read these and all
component instruc-
tions. Please keep for
future reference.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 150 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Bock Water heaters 150

  • Page 1 DO NOT INSTALL THE WATER HEATER ON COM- BUSTIBLE FLOORING. Install in accordance with all local codes. In the absence of local codes, refer to NFPA 31 or ANSI Z21.10.1, or contact Bock Water Heaters with questions concerning proper flooring materials. Minimum clearance to combustible construction is: SIDES 6”;...
  • Page 2: Burner Specifications

    200-1150 250-1250 250-1500 Leave ample room for servicing when the water heater is installed – do not block access to the burner, inspec- tion door, handholes or controls. Leave room to pipe the unit and connect the fuel and electricity.
  • Page 3 When pressure testing the gas supply piping system at less that 1/2 psig., close the manual gas shut-off valve to the heater. If test pressures are to exceed 1/2 psig., the water heater and its manu- al shut-off valve must be disconnected from the system. Be sure gas service and meter are ade- quately sized.
  • Page 4: Combustion Air

    NOTE: All ducts tions. Free circulation of air around the water heater is essential. If the air supply is inadequate, must have the introduce outside air. Any temperature above 90°F around the heater indicates a need for additional same cross sec- air (see NFPA 31 for air requirements).
  • Page 5 All wiring should conform to the National Electrical Code. Install a separately fused disconnect switch for the water heater. The water heater is equipped with an immersion aquastat with dual bulbs to control operation of the heater and a separate high limit immersion control (both controls are installed and wired at the factory).
  • Page 6 Check the oil filter gaskets and make sure the filter cartridge is nance will keep the clean. water heater operat- 4. If the burner motor does not run, check the motor thermal overload button (red) and reset. If the ing at peak efficien- burner motor does not run after pushing the red button on the back of the motor, turn the motor off cy.
  • Page 7: Maintenance

    Clean the oil burner nozzle annually and reset the electrodes. Replace the filter cartridge on the oil supply line filter annually. This warranty covers “Bock” Water Heaters models 150, 200 or 250, gas, oil or dual fuel. Bock WARRANTY Water Heaters, a division of Bock Corporation – a Wisconsin corporation – at 110 S. Dickinson St., COVERAGE Madison, WI 53703, (“Company”), warrants to the owner that the tank of this water heater will not...
  • Page 8 Rev. Date 01/05 #23432...