Below Grade Installations; Vertical Through The Roof Applications - Vermont Castings DBR33 Installation Instructions & Homeowner's Manual

Builder rear vent direct vent
Table of Contents

Advertisement

BELOW GRADE INSTALLATIONS

When it is not possible to meet the required vent terminal
clearances of 12 inches (305mm) above grade level a
model #7DVSKS vent kit is required. It allows installation
depth of down to 7 inches (178mm) below grade level. The
7 inches is measured from the centre of the horizontal vent
pipe as it penetrates through the wall.
If venting system is installed below ground,
we recommend a window well with adequate
and proper drainage.
Ensure sidewall venting clearances are observed.
The maximum horizontal run with 24" (610mm)
vertical rise is 36" (914mm) from the back of the
fireplace to the face of the exterior wall. See
vent graph (Fig. 21) for extended horizontal run
if the vertical exceeds 24" (610mm).
1. Establish vent hole through the wall. See page 14
2. Remove soil to a depth of approximately 16"
(406mm) below base of snorkel. Install window well
(not supplied). Refill hole with 12" (305mm) of
coarse gravel leaving a clearance of approximately 4"
(100mm)below snorkel. (Fig. 31)
3. Install vent system. See page 13, Steps 2 through 5.
4. Ensure a watertight seal is made around the vent
pipe coming through the wall.
5. Apply high temperature sealant caulking (supplied)
around the 4 and 7 inch 7DVSKS's snorkel collars.
6. Slide into vent pipe and secure to the wall.
7. Level the soil so as to maintain a 4"
(100mm)clearance below snorkel (Fig. 31).
DO NOT BACK FILL AROUND SNORKEL.
SOIL SHOULD NOT BE LESS THAN 4"
(100mm) BELOW SNORKEL.
If the foundation is recessed, use recess brackets (not
supplied) for securing lower portion of the snorkel. Fasten
brackets to wall first and then secure to snorkel with self
drilling #8 x 1/2 sheet metal screws. It will be necessary to
extend vent pipes out as far protruding wall face (Fig. 32).
This Gas Fireplace has been approved for,
a) Vertical installations up to 40 feet (12 metres) in height.
Up to a 10 ft.(3048mm) horizontal vent run can be
installed within the vent system using a maximum of
three 90
b) Up to two 45
run. For each 45
the maximum horizontal length must be reduced by 18
inches (457mm).
Example: Maximum horizontal length
c) A minimum of an 8 ft. vertical rise.
d) Two sets of 45 degree elbow offsets within these
vertical installations. From 0 to a maximum of 8 ft.
(2438mm) a vent pipe can be used between elbows.
Fig. 31
(Fig. 35)
e) 7DVCS must be used to support offsets. (Fig. 35)
This application will require that you first determine the roof
pitch and use the appropriate 7DVSKV (A,B or F). (see
Venting Components, page 28)
- 16 -
FOUNDATION
RECESS
SNORKEL
WATERTIGHT
SEAL
AROUND
PIPE
SCREWS
SHEET METAL
SCREWS
VERTICAL THROUGH THE
ROOF APPLICATIONS
MAXIMUM
10 FT
(3048mm)
MINIMUM
8 FT./
MAXIMUM
40 FT.
VERTICAL
RISE
PIPE STRAPS
EVERY 3'
(914mm)
o
elbows.
o
elbows may be used within the horizontal
o
elbow used on the horizontal level
o
0
- 45
elbows 10 ft. (3048mm)
o
1
- 45
elbows 8.5 ft. (2590mm)
o
2
- 45
elbows 7 ft. (2133mm)
WALL
Fig. 32
Fig. 33