DO NOT BACK FILL AROUND SNORKEL.
SOIL SHOULD NOT BE LESS THAN 4"
BELOW SNORKEL.
FOUNDATION
RECESS
WATERTIGHT
SEAL
AROUND
PIPE
If the foundation is recessed, use recess brackets (not
supplied) for securing lower portion of the snorkel. Fasten
brackets to wall first and then secure to snorkel with self
drilling #8 x 1/2 sheet metal screws. It will be necessary to
extend vent pipes out as far protruding wall face (Fig. 57).
VERTICAL THROUGH THE
ROOF APPLICATIONS
MINIMUM
8 FT./
MAXIMUM
40 FT.
VERTICAL
RISE
PIPE STRAPS
EVERY 3'
(914mm)
This Gas Fireplace has been approved for,
a) Vertical installations up to 40 feet (12 metres) in height.
Up to a 10 ft. horizontal vent run can be installed within
the vent system using a maximum of three 90
o
b) Up to two 45
elbows may be used within the horizontal
run. For each 45
o
elbow used on the horizontal level
the maximum horizontal length must be reduced by 18
inches.
Example: Maximum horizontal length
0
-
45
1
-
45
2
-
45
SNORKEL
WALL
SCREWS
SHEET METAL
SCREWS
MAXIMUM
10 FT
(3048mm)
o
o
elbows
10 ft.
o
elbows
8.5 ft.
o
elbows
7 ft.
c) A minimum of an 8 ft. vertical rise.
d) Two sets of 45 degree elbow offsets within these
vertical installations. From 0 to a maximum of 8 ft. a
vent pipe can be used between elbows. (Fig. 59)
e) 7DVCS must be used to support offsets. (Fig. 60)
This application will require that you first determine the roof
pitch and use the appropriate 7TDVSKV (A,B or F). (see
Venting Components, page 27)
Fig. 59
Fig. 57
SIDE VIEW
Fig. 58
40 FEET
(12.2m)
elbows.
The minimum height of the vent above the highest
point of penetration throught the roof is 2 feet. See
Fig. 62.
- 24 -
MAX. 8 Ft.
(2438mm)
MAX.
MAX. 8 Ft.
40 FEET
(12.2m)
(2438mm)
MIN.
8 FEET
(2.44m)
VENT TERMINATION
STORM COLLAR
ROOF FLASHING
ROOF
24" Min.
(610mm)
ATTIC INSULATION
JOISTS
ATTIC INSULATION
SHIELD
TYPICAL STRAIGHT-UP INSTALLATION
)
TYPICAL 7DVCS
Fig. 60
APPLICATION
Fig. 61
TYPICAL ROOF
SUPPORT
APPLICATION
ROOF SUPPORT
CEILING JOISTS
Fig. 62