Gree Versati III Series Owner's Manual page 13

Air-to-water heat pump split
Hide thumbs Also See for Versati III Series:
Table of Contents

Advertisement

SPLIT
TYPE
the required range.
Water heating: in water heating mode: the refrigerant evaporates in the outdoor unit and is condensed in
the indoor unit. Via the heat exchange with water in the indoor unit, the water absorbs heat and its temperature
increase while the refrigerant releases heat and is condensed. With the help of wired controller, the outflow
temperature can meet the user's requirement. Through the control of valve, the high-temperature water in the
system is connected with the coil pipe of bearing water tank, and exchanges heat with the water in the water tank
so that the temperature of water tank increases to the required range.
Cooling + water heating: when cooling mode exists together with the water heating mode, the user can set the
priority of these two modes based on the needs. The default priority is heat pump. That is under the default setting,
if cooling mode exists together with the water heating mode, the heat pump gives priority to cooling. In that case,
water heating can only realized with e-heater of the water tank. Inversely, the heat pump gives priority to water
KHDWLQJ DQG VZLWFKHV WR FRROLQJ DIWHU ¿QLVKLQJ ZDWHU KHDWLQJ
Heating + water heating: when heating mode exists together with the water heating mode, the user can set the
priority of these two modes based on the needs. The default priority is heat pump. That is under the default setting,
if heating mode exists together with the water heating mode, the heat pump gives priority to heating. In that case,
water heating can only realized with e-heater of the water tank. Inversely, the heat pump gives priority to water
KHDWLQJ DQG VZLWFKHV WR KHDWLQJ DIWHU ¿QLVKLQJ ZDWHU KHDWLQJ
Emergency mode: this mode is only available for heating and water heating. When the outdoor unit stops due
WR PDOIXQFWLRQ HQWHU WKH FRUUHVSRQGLQJ HPHUJHQF\ PRGH DV WR KHDWLQJ PRGH DIWHU HQWHULQJ WKH HPHUJHQF\ PRGH
KHDWLQJ FDQ RQO\ EH UHDOL]HG WKURXJK HKHDWHU RI WKH LQGRRU XQLW :KHQ WKH VHWWLQJ RXWÀRZ WHPSHUDWXUH RU LQGRRU
WHPSHUDWXUH LV UHDFKHG WKH HKHDWHU RI LQGRRU XQLW ZLOO VWRS UXQQLQJ DV WR ZDWHU KHDWLQJ PRGH WKH HKHDWHU RI
indoor unit stops while the e-heater of water tank runs. When the setting temperature or water tank is reached, the
e-heater will stop running.
Quick water heating: in quick water heating mode, the unit runs according to the water heating control of heat
pump and the e-heater of water tank runs at the same time.
Forced Operation Mode: this mode is only used for refrigerant recovery and debugging for the unit.
Holiday mode: this mode is only available for heating mode. This mode is set to keep indoor temperature or
leaving water temperature in a certain range, so as to prevent water system of the unit from freezing or protect
certain indoor articles from freezing damage. When the outdoor unit stops due to malfunction, the two e-heaters of
the unit will run.
Disinfection mode: in this mode, the water heating system can be disinfected. When starting up the disinfection
function and setting corresponding time to meet the requirement of disinfection mode, the function will start. After
the setting temperature is reached, this mode will terminate.
Weather-dependent Operation: this mode is only available for space heating or space cooling. In Weather-
dependent mode, the setting value (remote room air temperature or leaving water temperature) is detected and
controlled automatically when the outdoor air temperature is changed.
Quiet mode: Silent mode is available in cooling, heating and water heating mode. In silent mode, the outdoor
unit will reduce the running noise via automatic control.
Floor commissioning WKLV IXQFWLRQ LV LQWHQGHG WR SUHKHDW WKH ÀRRU SHULRGLFDOO\ IRU WKH LQLWLDO XVH
Air removal of the water system: this function is intended to replenish water and remove air in the water
system to make the equipment run at the stabilized water pressure.
Solar water heater: ZKHQ WKH FRQGLWLRQ IRU VWDUWLQJ WKH VRODU ZDWHU KHDWHU LV VDWLV¿HG WKH VRODU KHDWHU ZLOO VWDUW
to heat the circulation water. Then the heated water will go to the water tank and exchange heat with water in it. At
any condition, the solar water heater will be given priority for startup so as for energy conservation.
Other thermal: when the outdoor temperature is lower than the set point for starting other thermal and the unit
is under the error condition and the compressor has stopped for three minutes, then the other thermal will start to
supply heat or hot water to the room.
Air-to-water Heat Pump Split Versati
9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents