Alarm limits can be configured via the ALARM LIMITS menu. LED light ring behavior can be
configured via the RING menu.
5.3.2 View pressure reading
If the DISPLAY is set to "OFF", the LCD display will be blank under normal operation. To see a
digital pressure reading, simply press on the lens of Setra Lite.
5.3.3 Standby mode
For temporary instances where the Red/Green LED light ring status is not needed (e.g. room
is opened for extended cleaning), Setra Lite can be placed into STANDBY mode by pressing
the lens 3 times in a quick succession. The LED light ring glows yellow in STANDBY mode.
This mode is used when the room will be open longer than the "door delay" feature allows.
The maximum door delay is usually set by facility personnel to avoid false alarms caused by
intermittent door openings. The maximum door delay can be set for up to 999 seconds.
To bring the unit out of STANDBY mode and back into normal operation, press the lens 3 times
in quick succession.