R410A All DC Inverter V4+S Series 60Hz
 When the outdoor unit is higher than surrounding obstacles
Unit: mm(in.)
One row
Two rows
>1000(39-3/8)
More than two rows
 When the outdoor unit is lower than surrounding obstacles, to avoid cross connection of the outdoor hot air
affecting the heat exchange capabilities, please add an air director onto the exhaust hood of the outdoor unit
to facilitate heat dissipation. See the figure below. The height of the air director is HD (namely H-h). Please
make the air director on site.
84
>1000(39-3/8)
Front
>1000(39-3/8)
>1000(39-3/8)
Front
Front
>1000(39-3/8)
>1000(39-3/8)
Front
Front
>1000(39-3/8)
Front
Front
>1000(39-3/8)
Front
Front
>100(4)
>1000(39-3/8)
>1000(39-3/8)
Front
>1000(39-3/8)
Front
>100(4)
Front
Front
>100(4)
Front
>100(4)
MCAC-VTSM-2015-09
Installation