BAS Integration Manual 680_B Snow Melting Control 680 10/15 Snow Melting Replaces: 04/15 Introduction The Snow Melting Control 680 can communicate with a Building Automation System (BAS) using either BACnet ® BACnet MSTP or Modbus MSTP. ® ® This manual provides information about control parameters that can be accessed by building automation or management systems that use BACnet or Modbus communication.
BACnet Protocol Implementation Conformance Statement (PICS) Vendor Name: tekmar Control Systems Ltd. Vendor ID: 585 Product Name: Snow Melting Control 680 Product Model Number: 680 Application Software Version: J1243F Firmware Revision: J1243F BACnet Protocol Revision: 10 Product Description: The 680 is a control that operates an automatic snow melting system.
BACnet Analog Parameters Analog Input Object = AI Analog Value Object = AV Read = R Read/Write = R/W Object Name Data Read/ Units Range/Value Type Write Analog Input Objects 0 = Off, 1 = Idle, 2 = Storm, 3 = Melt, Operation No Units (95) 4 = Manual Override...
BACnet Binary Parameters Binary Input Object = BI Binary Value Object = BV Read = R Write = W Object ID Name Data Type Read / Write Units Range/Value Binary Input Objects Slab 1 Water No Units (95) 0 = Dry, 1 = Wet Slab 2 Water No Units (95) 0 = Dry, 1 = Wet...
Modbus Parameters Read = R Read/Write = R/W Read/ Register Parameter Name Units Type Format Range Write Input Registers (Starts at 40,000) Model Enum Input Firmware Revision Enum Input SVN revision Software (A= 1, B = 2, ... Application Version Enum Input Z = 26)
Page 7
Modbus Parameters Read = R Read/Write = R/W Melting Hours (low word) Hours Input 0 to 65535 Melting Hours (high word) Hours Input 0 to 65535 Heat Cycles (low word) Enum Input 0 to 65535 Heat Cycles (high word) Enum Input 0 to 65535 System Pump Run Time (low word)