08/14 Multi-Staging Replaces: 09/13 Introduction The Boiler Control 284 can communicate with a Building Automation System (BAS) using either BACnet IP or Modbus ® ® This manual provides information about boiler plant & system parameters that can be accessed by building automation or management systems that use BACnet ®...
284 Confi guration Ensure the 284 has the correct Application Mode & BAS Type settings before connecting to the BAS. To view menu selections in the 284, press & hold the Home button for 3 seconds. Setup View Menu Press...
BACnet Protocol Revision: 10 Product Description: The 284 is a control that operates up to four boilers to provide heating for multiple loads. The control uses Proportional Integral Derivative (PID) logic to accurately maintain target temperature and offers advanced features including communication capability with a Building Automation System (BAS).
BACnet Settings in the 284 BAS Menu ® Item Field Range Description BAS MONITOR OFF or ON Selects whether or not BAS monitoring is available. Default: OFF Note: This item is only available when APP MODE is set to either RSET, SETP, Access: ADV DDHW or EMS.
Page 5
BACnet Settings in the 284 BAS Menu ® Item Field Range Description BACNET BBMD IP 0 to 255, 0 to 255, 0 to 255, 0 to 255 Sets the BBMD IP address on the BACnet ® network. The address is set using four number sets displayed in the source output fields.
BACnet Analog Parameters ® Analog Input Object = AI Analog Value Object = AV Read = R Read / Write = R / W (n) represents the specific Boiler number, including 1, 2, 3 and 4. Object Name Description Data Read / Units Range / Value...
BACnet Binary Parameters ® Binary Input Object = BI Binary Output Object = BO Binary Value Object = BV Read = R Write = W (n) represents the specific Boiler number, including 1, 2, 3 and 4. Object ID Name Description Data Type Read / Write Units...
Modbus Settings in the 284 BAS Menu ® Item Field Range Description BAS MONITOR OFF or ON Selects whether or not BAS monitoring is available. Default: OFF This item is only available when APP MODE is set to either RSET, SETP, DDHW Access: ADV or EMS.
Modbus Parameters ® Read = R Read / Write = R / W (n) represents the specific Boiler number, including 1, 2, 3 and 4. Register Parameter Name Read /Write Units Type Format Range System Status Registers Boiler Target Temperature °F Input -22 to 266°F...
Modbus Parameters ® Read = R Read / Write = R / W (n) represents the specific Boiler number, including 1, 2, 3 and 4. Register Parameter Name Read /Write Units Type Format Range Boiler Status Registers 10,11,12,13 Boiler (n) Enable/Disable Enum Holding 0 = Enable, 1 = Disable...