Appendix B.7.2.2 ACS880 Drive Setup Instructions
1. Navigate to parameter group 58 (Embedded Fieldbus) and make the following adjustments to these
parameters:
58.01 = Modbus RTU
58.03 = 1
58.04 = 19.2 kbps
58.05 = 8 None 1
All other group 58 parameters should be left at their default setting. These parameter adjustments
allow the drive to communicate to the gateway.
Once the above settings are entered, power must be cycled on the drive to activate them. Make
sure the drive control panel goes blank before re-applying power.
2. If BACnet is only used to monitor the drive, skip all of step 2.
To control the drive's run/stop and/or speed over BACnet, update the following settings on the
ACS880.
a. Setup Run/Stop control over BACnet.
b. Setup Frequency/Speed Control over BACnet by checking the settings below.
i.
Identify the Motor control setup being used: DTC or Scalar mode
Page 37 of 46
ABB ProtoNode Start-up Guide