Hardware Installation; Initial Checks; Installation Location; Installation In Hazardous Areas - GE IC695ETM001 Manual

Ethernet interface module for pacsystems rx3i
Table of Contents

Advertisement

4
GFK-2332W

Hardware Installation

Initial Checks

Upon receiving your RX3i equipment, carefully inspect all shipping containers for damage. If any part of the system is
damaged, notify the carrier immediately. The damaged shipping container should be saved as evidence for inspection
by the carrier.
As the consignee, it is your responsibility to register a claim with the carrier for damage incurred during shipment. GE
Intelligent Platforms will fully cooperate with you, however, should such action be necessary.
After unpacking the RX3i equipment, record all serial numbers. Serial numbers are required if you should need to
contact Customer Care during the warranty period. All shipping containers and all packing material should be saved
should it be necessary to transport or ship any part of the system.
Verify that all components of the system have been received and that they agree with your order. If the system received
does not agree with your order, contact Customer Care.

Installation Location

This product is intended for use with the RX3i system. Its components are considered open equipment (having live
electrical parts that may be accessible to users) and must be installed in an ultimate enclosure that is manufactured to
provide safety. As a minimum, the enclosure shall provide a degree of protection against solid objects as small as
12mm (e.g. fingers). This equates to a NEMA/UL Type 1 enclosure or an IEC60529 IP20 rating providing at least a
pollution degree 2 environment. For details about installing RX3i rack systems, refer to GFK 2314.
If you need technical help, contact Technical Support. For phone numbers and email addresses, see the back cover of
this Guide.

Installation in Hazardous Areas

The following information is for products bearing the UL marking for Hazardous Areas or ATEX marking for explosive
atmospheres:
CLASS 1 DIVISION 2 GROUPS ABCD
This equipment is an open-type device and is meant to be installed in an enclosure suitable for the
environment that is only accessible with the use of a tool.
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations, or nonhazardous locations
only.
Warning – EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I,
DIVISION 2.
Warning – WHEN IN HAZARDOUS LOCATIONS, TURN OFF POWER BEFORE REPLACING OR WIRING MODULES;
AND
Warning – DO NOT CONNECT OR DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE
AREA IS KNOWN TO BE NONHAZARDOUS.
Warning – EXPLOSION HAZARD - USB PORT IS ONLY FOR USE IN NONHAZARDOUS LOCATIONS, DO NOT USE
UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS.
ATEX Zone 2
This product must be mounted in an enclosure certified in accordance with EN60079-15 for use in Zone 2, Group IIC
and rated IP54. The enclosure shall only be able to be opened with the use of a tool.
RX3i Ethernet Interface Module IC695ETM001-HV IPI
February 2016