Auto restart
NOTE
• When outdoor unit only power supply change by local condition, it is an option to auto restart system .
Classification
Hydro Unit
(default)
operation
according to
the DIP S/W #4
setting
– The outdoor unit on/off control is not available with the A2A indoor unit.
– Although the outdoor unit is turned on after the E101 error occurred, the A2A indoor unit operation keeps
turned off.
DIP switch
ON
1
2
When the outdoor unit is power
ON
• Hydro Unit E101 error occurs.
• Hydro Unit E101 error occurs.
OFF
3
4
off
• Hydro Unit E101 error disappears.
• Hydro Unit operation turns off.
• Hydro Unit E101 error disappears.
• Hydro Unit keeps its previous
ENGLISH-50
When the outdoor unit is power on
operation.