Pipe work
ESP(External Static Pressure) Diagram
The illustration below shows the external static pressure of the unit depending on the water flow and the pump setting .
ESP [kPa]
90
80
70
60
50
43
40
30
20
10
0
15
20
10
If the pressure loss of total system is over 43(9 kW) or 20(16 kW)kPa, additional water pump should be installed in series .
Otherwise, the flow rate might decreased, causing insufficient heating or cooling .
When ESP is not enough, additional pump should be installed . In this case, install the PWM control external type pump
(Heating type) additionally .
Connection guide of additional pump
Case 1) INV. pump
Connect the PWM control external type pump to PWM terminal block and power cable to the external contact terminal .
The maximum number of additional pump installation is one inverter pumps (Input power 100W) .
1 . Power supply (For additional INV . Pump)
B1
B6
Live additional pump
Neutral additional pump
2 . PWM control (For additional INV . Pump only), refer to page 24, 25
Reference (GND)
PWM signal (SIG)
• If there is wrong wiring between PWM and reference, INV . Water Pump may not work or wrong operation .
CAUTION
16 kW
9 kW
2526
30
35
Water flow rate
9 kW : 26 LPM
ENGLISH-18
Flow [l/min]
40
4546
50
Water flow rate
16 kW : 46 LPM