USSC Hotblast 1200Q Owner's Manual page 7

Solid fuel warm air furnace
Table of Contents

Advertisement

LOCATING THE FURNACE
1.
The furnace should be located in the same
room as the central system and as close as
possible, but no closer than 9". There should be
no wall between the furnace and the warm air
outlet duct that is connected directly to the
warm air outlet plenum of the central furnace.
See Fig. 2.
2.
The unit will require installation with the
following clearances:
Unit to sidewall . . . . . .12" (305 mm)
Unit to backwall . . . . . 30" (760 mm)
Chimney connector pipe to sidewall
. . . . . . . . . . . . . . . . . . 21" (530 mm)
Chimney connector pipe to backwall
. . . . . . . . . . . . . . . . . . 18" (460 mm)
Hot air ducts to combustibles
. . . . . . . . . . . . . . . . . . . 6" (150 mm)
NOTE: Install only on a noncombustible
floor. (REFER TO FIG. 2 & 3)
3.
Place the furnace on a noncombustible floor.
4.
Check figures 2 and 3. Be sure you have the
clearances shown from the furnace and the
connector pipe to combustible surfaces. If you
have a solid brick or stone wall behind your
heater, you can place the furnace as close as
you wish to the wall. If the wall is only faced with
brick or stone, treat it as a combustible wall.
•DRAWINGS FOR ILLUSTRATION PURPOSES ONLY•
FIG. 3
FIG. 2
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents